System Paci/Ecoi Dhw - Panasonic PAW-VP1000LDHW Installation Manual

Air-to-water heat pump systems, domestic hot water system for r410a and r32 use
Hide thumbs Also See for PAW-VP1000LDHW:
Table of Contents

Advertisement

5.2

System PACi/ECOi DHW

 Standard system
with circulation pipe and
temperature control system
1
(Field supplied) accessories
A Pressure control valve if inlet city water is
more than 6 bar (field supplied)*
B Strainer (field supplied)*
C Expansion tank if check valve or pressure
control valve is mounted (field supplied)
D Circulation water pump (e.g. Grundfos
comfort UP 15–14 BA PM, field supplied)
For a hotel or apartment complex where the last room is more than 30 meters away from the
DHW tank, a water pump (for example type Grundfos comfort UP 15-14 BA PM) should be
installed in order to obtain hot water quickly.
Remember to install a return pipe for pump circulation of maximum Ø15 mm and make sure that
supply and return pipes are well insulated for minimal heat loss.
* This is supplied in UK as part of optional accessory (PAW-G3KITL).
** For models PAW-750LDHW-1 and PAW-1000LDHW-1. The pressure temperature relief valve is factory
fitted as standard.
DHW PAW-VP - Installation manual – 2020-05
2
7
City Water in
3
System drawings
6
7
5
Ø15 mm max.
E Safety valve 6 or 9.5 bar (field supplied)**
F Temperature control valve (field supplied)
G Water pipe inlet/outlet VP1000L/750
(35 mm) VP500L/200 (22 mm)
H PAW-VP-RTC5B-PAC/VRF controller
4
DHW
8
33
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Paw-vp750ldhwPaw-vp380l

Table of Contents