Fb12 "Linemodule_Fb - Siemens SINAMICS S Series Short Description

Speed control step7 v5 via profinet/profibus with safety integrated via profisafe and hmi
Hide thumbs Also See for SINAMICS S Series:
Table of Contents

Advertisement

2 Explanation of the Blocks

2.2 FB12 "LineModule_FB"

Parameter
Input_Address
Output_Address
Alarm_Present
Fault_Present
Group_Alarm_Present
Group_Fault_Present
DI_nn (n = 00...15)
Alarm_Code
Fault_Code
Retval_RD
Retval_WR
All of the above input parameters have an initial value of 0 or FALSE.
Access to the individual CU_STW1 bits – with the exception of
Acknowledge_Faults – is not supported by FB11.
2.2
FB12 "LineModule_FB"
The FB coordinates the cyclic process data transfer between the PLC and the Line
Module (A_INF) of the SINAMICS S120 on the basis of the extended SIEMENS
frame 370. This requires the drive (STARTER) as well as the controller (STEP 7,
HW Config) to be configured with the SIEMENS frame 370 that was extended by
the alarm and error code.
With the extended SIEMENS frame 370 the following data is exchanged:
Table 2-3: Data transferred with the extended SIEMENS frame 370
PZD
Wor
S7-300/400F
d
1
E_STW1 (A_INF control word)
2
3
Details on the frame contents can be found in the SINAMICS S120/S150 list
manual in chap. 2.3 (/7/).
The FB12 uses the system functions SFC14 and SFC15.
With regard to the line module you can do the following with FB12 ...
switch it on and off,
request the status (ready for switch-on, in operation, PLC control requested),
acknowledge errors
detect pending alarms and errors.
SINAMICS S120 at S7-300/400F
Entry-ID: 68624711,
V1.1,
Data
type
Word
Word
Output parameters
BOOL
BOOL
BOOL
BOOL
BOOL
Int
Int
Int
Int
SINAMICS S120
12/2014
Description
CU_S I/O input address
(from HW Config or STARTER)
CU_S I/O output address
(from HW Config or STARTER)
CU_S: alarm pending.
CU_S: fault pending.
CU_S: group alarm pending.
CU_S: group fault pending.
Read out of CU digital input nn.
Alarm code of a pending CU_S alarm.
Error code of a pending CU_S fault.
Error information of SFC14
(output parameter RET_VAL of SFC14)
Error information of SFC15
(output parameter RET_VAL of SFC15)
SINAMICS S120
E_ZSW1 (A_INF status word)
WARN_CODE
FAULT_CODE
S7-300/400F
8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics s120Simatic s7-300fSimatic s7-400f

Table of Contents