Vacuum circuit breakers – fixed type 4.8 & 7.2kv voltage classes
Table of Contents

Advertisement

INSTALLATION

Do not install this
WARNING
equipment in areas where
unusual service conditions
exist. Using this equipment
in other than usual service
conditions can result in
equipment failure.
Toshiba HV6AS circuit breakers are intended for
use in usual service conditions as defined in
IEEE C37.20.2. The temperature of the cooling
air (ambient air temperature) surrounding the
breaker should be between the limits of -5°C
(23°F) and +40°C (104°F). The altitude of the
equipment installation should not exceed 3300 ft
(1000 m).
In particular, avoid the following installation
conditions:
-
Excessive dust
-
Corrosive gases
-
Extreme variations in temperature
-
Very high or low humidity
Vibrations
-
Inclined locations
-
If there is a chance that condensation can occur
Fig. 8 Typical Circuit Breaker Nameplate
RATED VOLTAGE
FREQUENCY
CONTINUOUS AMPS
IMPULSE LEVEL
DIELECTRIC
WEIGHT
PARTS & WIRING, SEE INSTRUCTIONS
SER. No.
TOSHIBA
VACUUM CIRCUIT BREAKER
TYPE
HV6AS-
7.2/4.8 kV, RMS
50/60 Hz
630A, RMS
60 kV, CREST
22 kV AC RMS
24
kg
53
lbs
98700221
TOSHIBA INTERNATIONAL CORPORATION
HOUSTON, TEXAS U.S.A.
at the installation location, a space heater should
be installed inside the circuit breaker enclosure.
NOTE:
Temperature,
conditions outside of the usual limits
may require derating or other special
equipment.
Toshiba representative for additional
information.

RATING VERIFICATION

Prior to Installation, the maximum fault current
capacity of the power system at the point of
installation should be verified. This value must
not
exceed
capability of the circuit breaker.
illustrates a typical circuit breaker nameplate.
DANGER
MU-VV
SHORT CKT. AMPS
INTERRUPTING TIME
CLOSE VOLTS
SHUNT TRIP VOLTS
UV TRIP VOLTS
MFG. STANDARD
GF07Z301
MFG. DATE
7/98
Page 11
altitude
Contact
your
the
symmetrical
interrupting
Do not exceed the ratings
specified on the circuit
breaker nameplate or
system accessories.
Underrated equipment can
fail during operation
causing fire, explosion,
severe injury, death, and
property damage.
14/16 kA, RMS
3 CYCLES
120 VAC / 125
VDC
125
VDC
120 VAC
JIS C 4603-1990
JEC-2300-1985
or
other
nearest
Fig. 8