Huawei NetCol5000-C Series User Manual page 44

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Category
3-9
Figure 3-9 Connecting water inlet and outlet pipes
(1) Reserved port (1 inch, BSPT,
external threaded connector)
(4) Rubber hose (DN25
recommended, subject to
engineering procurement)
(7) Stainless corrugated hose (1
inch, BSPP, internal threaded
connector, DN25 recommended,
length 200 mm recommended,
subject to engineering
procurement)
The following table describes the cable specifications.
Issue 09 (2020-01-10)
Required Materials
sealing gasket
(2) Pagoda connector
(DN25, standard
configuration)
(5) Conversion adapter (1
inch, BSPP, internal
threaded connector,
subject to engineering
procurement)
(8) Steel pipe (DN25,
recommended, subject to
engineering
procurement)
Copyright © Huawei Technologies Co., Ltd.
Operation
reserved port and steel pipe opening, and
connect the pipe to the steel pipe and
reserved port using conversion adapters at
both ends.
(3) Hose clamp (standard
configuration)
(6) Rigid PPR or
aluminum-plastic pipe
(DN32 recommended,
subject to engineering
procurement)
3 Installation