Current Loop Specifications; Panel Specifications - GE 1200 Series Interconnection And Wiring Manual

Fire panels, repeaters, and emulators
Table of Contents

Advertisement

6.2

Current loop specifications

Maximum number of devices .......................................................................................................................................................... 15
Maximum distance between devices...................................................... max. 1 km between 2 current loop devices
Cable capacitance............................................................................................................................................................ max. 150 nF
Current loop is not supported in panels with software v8.xx and later.
Aritech FM800 / FR800 German fire brigade panel (according to DIN 14661) can be connected.
6.3

Panel specifications

Standard outputs
The following standard outputs are located on the sounder board:
OUT1 - alarm devices (sounders)
OUT2 - fire routing equipment (fire brigade)
OUT3 - fire protection equipment
OUT4 - fault warning routing equipment
OUT5 - OUT8 - four programmable relays (each with C, NO, NC terminals)
The maximum supervision for all supervised outputs is 5 V.
Output
A/B
OUT1
A
B
OUT2
A
B
OUT3
A
B
OUT4
A
B
OUT5 – OUT8
* The maximum specified current of 100 mA for Output 1 and Output 2 can be exceeded as long as the total current drawn
by the outputs (1-4) is limited to 400 mA.
FP1x00 & FP1216 (SD1200 card)
24 V – 100 mA supervised*
3K3/680 Ohm switched output
24 V – 100 mA supervised*
3K3/680 Ohm switched output
24 V – 100 mA supervised*
3K3/680 Ohm switched output
24 V – 100 mA supervised*
3K3/680 Ohm switched output
Maximum switching current: 2 A @ 24 VDC
Maximum power rating: 60 W DC
1200-2000 Series Fire Panels, Repeaters, and Emulators
Interconnection and Wiring Guide
FP1216EN & FP1264/2xxx & FP1216N /
FP1264N (SD2000 card)
24 V - 0.8 A supervised
3K3/680 Ohm switched output
24 V - 0.8 A supervised
3K3/680 Ohm switched output
24 V - 0.1 A supervised
3K3/680 Ohm switched output
24 V - 0.1 A supervised
3K3/680 Ohm switched output
Maximum switching current: 2 A @ 24 VDC
Maximum power rating: 60 W DC