Huawei PowerCube 500 User Manual page 45

Hide thumbs Also See for PowerCube 500:
Table of Contents

Advertisement

PowerCube 500 (CPS300-N18A1H)
User Manual
Indicator
Status
Issue 02 (2019-08-30)
Alarm Name
Possible Cause
DC Overvolt.
The DC overvoltage
alarm threshold is
incorrectly set.
DC Undervolt.
The battery voltage
is below the
undervoltage alarm
threshold after a
long-time AC
power failure.
The DC
undervoltage alarm
threshold is
incorrectly set.
Power module
The module
Update Failed
experiences a
power failure
during an upgrade.
The module
experiences a
communication
failure during an
upgrade.
The lithium battery
ESMU Missing
Copyright © Huawei Technologies Co., Ltd.
5 Alarms and Troubleshooting
Solution
incorrectly set.
If yes, reset the threshold.
If no, contact Huawei
technical support.
1. Reset the DC overvoltage
alarm threshold and check
whether the alarm persists.
If yes, contact Huawei
technical support.
If no, no further action is
required.
1. Check whether the battery
voltage is below the
undervoltage alarm threshold
after a long-time AC power
failure.
If yes, rectify the power
grid fault.
If no, go to the next step.
2. Check whether the DC
undervoltage alarm threshold
is incorrectly set.
If yes, reset the alarm
threshold.
If no, contact Huawei
technical support.
1. Check whether the function
module experiences a power
failure.
If yes, ensure that the
function module is
properly powered on.
If no, go to the next step.
2. Check whether the solar
function unit communicates
properly. Ensure that the
communication is proper,
continue the upgrade, and
check whether the alarm
persists.
If yes, replace the
function module.
If no, no further action is
required.
1. Check whether the lithium
39