Communications Services - Siemens CP 342-5 Manual

Communications processor for connection of simatic s7-300 / to profibus dp
Hide thumbs Also See for CP 342-5:
Table of Contents

Advertisement

Application and functions

1.3 Communications services

1.3
Communications services
Supported communications services
The current version of the CP 342-5/342-5 FO supports the following communications
services:
● PROFIBUS DP
– as DP master class 1 (PROFIBUS DP according to EN 50170 DPV0, DP master)
– as DP slave (PROFIBUS DP according to EN 50170 DPV0, DP slave)
● S7 communication and PG/OP communication
– PG functions with uploading / downloading of FM modules, configuration / diagnostics
– Operator control and monitoring functions (HMI)
– Client and server for data exchange via communication blocks on S7 connections
– Server for data exchange on connections configured at both ends without
● Open communications services (SEND/RECEIVE interface) over FDL connections of the
following type:
– Specified FDL connections
10
Note
DP master or DP slave
Please note, however: The CP 342-5/342-5 FO supports operation as a DP master or
DP slave only as alternatives. You can also deselect DP mode altogether.
and routing
Multiplexing TD/OP connections
When multiplexing OP connections, the following acyclic services are supported:
- read once
- write once
- read system status list
configured at both ends
The following blocks / functions are available:
BSEND FB 12, BRCV FB 13,
PUT FB 14, GET FB 15
USEND FB 8, URCV FB 9
C_CNTRL FC 62
You will find a more detailed description in /5/ (Page 48)
Note
The partner station can be an S7-300, S7-400 or PG/PC application with SIMATIC
NET OPC server; raw data tags using BSEND/BRECV to WinCC are not supported.
communications blocks on the S7-300 / C7-300 station
CP 342-5 / CP 342-5 FO
Manual, 07/2017, C79000-G8976-C146-10