SETTING AND USING METHOD
14
- Detail of the control step for analog input signal
SW_ STEP
Input Voltage
0
1
2
3
4
C
5
6
7
8
9
10
0
1
2
3
4
D
5
6
7
8
9
10
0
1
2
3
4
E
5
6
7
8
9
10
Cooling
Evaporating
Operation rate
Temp. [°C]
Comp off
Comp off
0%
Comp off
11.0
40%
9.8
45%
9.0
50%
7.2
60%
5.9
70%
5.0
80%
4.1
90%
3.1
100%
No control
-
3.1
100%
4.1
90%
5.0
80%
5.9
70%
7.2
60%
9.0
50%
9.8
45%
11.0
40%
Comp off
0%
All off
0%
Comp off
0%
11.0
40%
9.8
45%
9.0
50%
7.2
60%
5.9
70%
5.0
80%
4.1
90%
3.1
3.1
100%
3.1
Heating
Condensing
Operation rate
Temp. [°C]
Comp off
Comp off
0%
Comp off
31.3
40%
33.3
45%
34.5
50%
37.5
60%
40.4
70%
43.1
80%
45.6
90%
48.1
100%
No control
-
48.1
100%
45.6
90%
43.1
80%
40.4
70%
37.5
60%
34.5
50%
33.3
45%
31.3
40%
Comp off
0%
All off
0%
Comp off
0%
31.3
40%
33.3
45%
34.5
50%
37.5
60%
40.4
70%
43.1
80%
45.6
90%
48.1
48.1
100%
48.1
Type of input
Analog input
Analog input
Analog input