Warnings - ABB ABILITY SSC600 Operation Manual

Smart substation control and protection for electrical systems
Hide thumbs Also See for ABILITY SSC600:
Table of Contents

Advertisement

Troubleshooting
The internal fault code indicates the type of internal IED fault. When a fault appears, the
code must be recorded so that it can be reported to ABB customer service.
Fault indication
Internal Fault System error
Internal Fault File system error
Internal Fault Test
Internal Fault
SW watchdog error
Internal Fault License check fail 117
5.3.2

Warnings

Warnings are shown in the event list of the WHMI. The text Warning additionally provided
with the name of the warning, a numeric code as well as the date and time is shown on
the WHMI. The warning indication message can be manually cleared.
Table 11: Warning indications and codes
Warning indication
Warning IEC61850 error
Warning Dataset error
Warning
Report cont. error
Warning
GOOSE contr. error
Warning
SCL config error
Warning Logic error
Warning
SMT logic error
Warning
GOOSE input error
ACT error
Warning
GOOSE Rx. error
54
Fault code
2
7
8
10
Note: If a warning appears, record the name and code so that it can be
provided to ABB customer service.
Warning code
20
24
25
26
27
28
29
30
31
32
1MRS758850
Additional information
An internal system error has
occurred.
A file system error has occur-
red.
Internal fault test activated
manually by the user.
Watchdog reset has occurred
too many times within an hour.
The devices is equipped with
invalid license.
Additional information
Error when building the IEC
61850 data model.
Error in the Data set(s).
Error in the Report control
block(s).
Error in the GOOSE control
block(s).
Error in the SCL configuration
file or the file is missing.
Too many connections in the
configuration.
Error in the SMT connections.
Error in the GOOSE connec-
tions.
Error in the ACT connections.
Error in the GOOSE message
receiving.
SSC600