7.3. Conduit mounting method
(1) Fasten the indoor unit wire harness to the conduit holder using the lock nut.
IMPORTANT: Refer to [7.1. Wiring system diagram] about the length of indoor unit wire
harness.
(2) Remove the screws, then remove the cable clamper.
(3) Connect indoor unit wire harness to the terminal.
Refer to the wiring diagram
(4) Use the screws to install the cable clamper.
] 1
7.4. How to connect wiring to the terminals
Caution when wiring cable
When stripping off the insulation of a lead wire, always use a special tool such as a wire
stripper. If there is no special tool available, carefully strip the insulation with a knife etc.
(1) Use crimp-type terminals with insulating sleeves as shown in the figure below to
connect to the terminal block.
(2) Securely clamp the crimp-type terminals to the wires using an appropriate tool so that
the wires do not come loose.
Strip: 10 mm (6/16 in.)
(3) Use the specifi ed wires, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a
screwdriver that is too small, otherwise, the screw heads may be damaged and
prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
Screw with special washer
Crimp-type terminal
Wire
Terminal blocks
(6) See the table below for the terminal screw tightening torques.
Tightening torque [N·m (kgf·cm)]
M4 screw
Match the terminal block numbers and connection cable colors with those of the
outdoor unit or branch box.
Erroneous wiring may cause burning of the electric parts.
Connect the connection cables fi rmly to the terminal block. Imperfect installation may
cause a fi re.
Always fasten the outside covering of the connection cable with the cable clamp. (If
the insulator is chafed, electric discharge may occur.)
Always connect the earth (ground) wire.
Do not use the earth (ground) screw of the indoor unit for the connection other than a
specifi ed outdoor unit or branch box.
En-8
Lock nut
Conduit
holder
Conduit
connector
Crimp-type
terminal
Sleeve
Screw with
special washer
Crimp-type
terminal
Wire
1.2 to 1.8 (12 to 18)
CAUTION
] 1 ] 1

8. FINISHING

(1) Insulate between pipes.
• Overlap the connection pipe heat insulation and indoor unit pipe heat insulation.
• Wrapping the connection pipe with cloth tape over the range within which they fi t into
the rear piping housing section.
• Fasten the pipe bracket with the screw.
(2) Fixing the pipe and conduit with cable ties.
(3) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and wind cannot blow in.
(4) Fasten the drain hose to the outside wall, etc.
Pipe
bracket
Screw
Left piping
Connection wire
Pipe
Drain hose
Check the following:
GOOD
Stopping
downward
End of drain hose
is immersed in
water.
Drainage
channel

9. TEST RUN

Do not turn on the power until all installation work is complete.
When restarting after a long period of disuse in the winter, turn the power switch on at
least 12 hours before starting the unit.
Check items
(1) Is operation of each button on the remote controller normal?
(2) Does each lamp light normally?
(3) Do air fl ow direction louvers operate normally?
(4) Is the drain normal?
(5) Do not have an abnormal noise and vibration during operation?
● Do not operate the air conditioner in test run for a long time.
Cloth
Front side of
tape
pipe bracket
Conduit
Wrap the each pipe
with cloth tape
For connection from the left rear
Connection wire
Wall pipe
Connection
pipe
Drain hose
Conduit
PROHIBITED
Accumulated
No upward
drain water
slope
50 mm (1-15/16 in.)
or less from ground
WARNING
CAUTION
Pipe
Cable tie
Air
No upward
slope