Troubleshooting; Flow Rate Is Not Indicated - Toshiba LF414 Instruction Manual

Electromagnetic flowmeter detector
Hide thumbs Also See for LF414:
Table of Contents

Advertisement

7.2 Troubleshooting

If a problem occurs while using the LF414/LF600F, LF414/LF610F and LF414, follow the flowcharts
described below.
You may find a way to solve the problem. The flowcharts are based on three symptoms (1) to (3).
If you cannot solve the problem, contact your nearest Toshiba representative.

7.2.1 Flow rate is not indicated

Are power supplies correct
for each device?
Are power and I/O cables
installed correctly?
Is the fuse burnt?
Is the flow range correctly set?
Is the flow direction match
with the arrow mark on the
detector?
Contact your nearest Toshiba
representative.
START
YES
YES
NO
YES
YES
NO
Use the correct power supply for each
device.
Install the cables correctly.
NO
Refer to Chapter 5, "Wiring."
YES
Replace the fuse with a new one.
Set correctly.
NO
Refer to combined converter's manual.
Install the detector correctly.
NO
Refer to Chapter 4, "Installation"