Types
There are 2 types of mains filter for IndraDrive M drive controllers to
ensure interference suppression according to EN61800-3, class A,
group 2 and 1 type to ensure interference suppression according to
EN61800-3, class B, group 1:
• Type 1:
For max. 6 axis with a total motor cable length of 240 m.
• Type 2:
For max. 15 axis with a total motor cable length of 900 m.
• Type 3:
For max. 6 axis with a total motor cable length of 100 m.
For IndraDrive C drive controllers you only need filters Type 1 or Type 3.
Features
• mains voltages which can be connected: 380V -15% to 480V +10%
• appropriate mains systems: TN, TT, IT
• maximum allowable ambient temperature: 40 °C (without derating)
resp. 55 °C (with 2% derating per °C to 40 °C)
• filters are UL listed