Technical data of RDD100.1RF
Power supply
Function data
Environmental conditions
Standards and directives
Environmental
compatibility
Eco design and
labelling directives
General
Siemens
Building Technologies
Operating voltage
For battery life (RDD100.1RF), see below (alkaline batteries type AAA).
Battery life calculation is based on the touchpad scanning rate during idle time
(assuming a user presses 4 touchkeys per day):
Scanning rate 0.25 s
Scanning rate 0.5 s
Scanning rate 1 s (default)
Scanning rate 1.5 s
Switching differential SD
Comfort mode
Economy mode
Built-in room temperature sensor
Setpoint setting range
Accuracy at 25 °C
Temperature calibration range
Resolution of settings and displays
Setpoints
Temperature value displays
Operation
Climatic conditions
Temperature
Humidity
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Storage
Climatic conditions
Temperature
Humidity
EU Conformity (CE)
RCM conformity
Safety class
Pollution class
Degree of protection of housing
The product environmental declaration CE1E1420xx
environmentally compatible product design and assessments (RoHS compliance,
materials composition, packaging, environmental benefit, disposal).
Based on EU Regulation 813/2013 (Eco design directive) and 811/2013 (Labelling
directive) concerning space heaters, combination heaters, the following classes
apply:
-
Application with On/Off
operation of a heater
Connection terminals for
Weight
Color of housing front
*) The documents can be downloaded from http://siemens.com/bt/download.
RDD100.1RFS
Wireless room thermostat with LCD
DC 3 V (2 x 1.5 V alkaline batteries AAA)
311 days battery life
322 days battery life
357 days battery life
377 days battery life
1 K
20 °C (5...35 °C)
16 °C (5...35 °C)
5...35 °C (Comfort/Economy mode)
<±0.5 K
±3.0 K
0.5 °C
0.5 °C
As per IEC 60721-3-3
Class 3K5
0...50 °C
<95% r.h.
As per IEC 60721-3-2
Class 2K3
-25...60 °C
<95% r.h.
Class 2M2
As per IEC 60721-3-1
Class 1K3
-25...60 °C
<95% r.h.
*)
CE1T1420xx
*)
CE1T1420en_C1
II as per EN 60730-1, EN 60730-2-9
II as per EN 60730-1
IP30 as per EN 60529
*)
contains data on
Class I
value 1%
Solid wires or prepared stranded wires
2
2 x 1.5 mm
or 1 x 2.5 mm
0.152 kg
RAL9003
2
2
(Min. 0.5 mm
)
9 / 13
CB1N1424en
2017-11-21

Advertisement

loading

This manual is also suitable for:

Rcr100rfRdd100.1rfs