Room thermostats with knx communications (180 pages)
Summary of Contents for Siemens QMX2.P33
Page 1
Wall-mounted sensors and room operator units for KNX PL-Link QMX2.P33 / QMX2.P43 Communicative sensors and room operator units with KNX PL-Link (for Desigo™ To- tal Room Automation). ● Room temperature and humidity measurement (depending on types) ● LCD display of room temperature, operating modes, etc.
Page 2
- Reset device to factory settings (button 4) Note: This operation is irreversible! ● Indicates that the room operator unit is locked by the system. - Operation disabled - Display in line 1 shows the temperature from bus Siemens A6V10733768_en--_a 2017-07-28...
Document ID: Installation, cable length, topology Mounting instructions A6V10733759 CE declaration A5W90002237 Product environmental declaration A5W90002450 All documents can be downloaded from http://siemens.com/bt/download. Notes The subsections include important information for sale or that is essential for engineering. Siemens A6V10733768_en--_a 2017-07-28...
Page 4
Do not mount the devices in recesses, shelves, behind curtains or doors, or above or near heat sources. ● Avoid direct solar radiation and drafts. ● Seal the conduit box or the installation tube if any, as air currents can affect sensor readings. ● Adhere to allowed ambient conditions. Siemens A6V10733768_en--_a 2017-07-28...
When the configuration is faulty, "Unconfigured" is displayed along with the temperature measured by the local temperature sensor. In this case, manual commissioning must be performed (see below). Siemens A6V10733768_en--_a 2017-07-28...
Page 6
The display shows the result of the connection test ("DONE" or "FAIL"). 2. Press button 8 to return to the engineering page. Reset to factory settings NOTICE This operation resets all user-defined data and configuration settings to factory default This operation is irreversible. Siemens A6V10733768_en--_a 2017-07-28...
Page 7
- If the test is positive, the LED is lit continuously. - If the test fails, the LED flashes (1s on, 1s off). 2. Briefly press the programming pin (<0.5s) to stop displaying the result of the connection test. The service LED goes off. Siemens A6V10733768_en--_a 2017-07-28...
Comply with all local and currently applicable laws and regulations. Warranty Technical data on specific applications is valid only together with Siemens products listed in "Equipment combinations". Siemens rejects any and all warranties in the event that third- party products are used.
Temperature -25...70 °C (-4... 158 °F) Air humidity <95% rh. Mechanical ambient conditions Normal operation Class 3M2 Transport Class 2M2 Standards, directives and approvals EU conformity (CE) A5W90002237 *) RCM conformity to EMC emission standard A5W90002243 *) IC compliance CAN ICE-3(B)/NMB-3(B) Siemens A6V10733768_en--_a 2017-07-28...
*) Documents can be downloaded at the following address: http://siemens.com/bt/download NOTICE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
Page 11
RJ45 plug of the tool cable Connector Description Description CE+, KNX Voltage 16 V CE-, KNX Unused Unused Identification pin Unused Ground Connection diagrams Operation The device - room operator unit The controller - room automation station Twisted pair Siemens A6V10733768_en--_a 2017-07-28...
Page 12
Service tool Connect ABT to load the application in the controller, or for service purposes: ● Directly to the controller ● To the device using the tool cable and the OCI702 service interface (see data sheet A6V10438951) Dimensions Siemens A6V10733768_en--_a 2017-07-28...