General
Risk of burns due to high surface temperature of the dv/dt filter compact
The surface temperature of the dv/dt filters compact may exceed 80° C. You can get
seriously burnt when touching the surface.
• Mount the dv/dt filters compact so that they cannot be touched. If this is not possible,
NOTICE
Damage to the Voltage Peak Limiter due to interchanged connections
The Voltage Peak Limiter will be damaged if the input and output connections are
interchanged on devices with the order numbers 6SL3000-2DE41-4EA0 and 6SL3000-
2DG38-1EA0.
• Connect the incoming cable from the DC link of the Power Module to DCPS, DCNS.
• Connect the outgoing cable for the dv/dt reactor to 1U2, 1V2, 1W2.
NOTICE
Damage to the dv/dt filter compact by using components that have not been released
When using components that have not been released, damage or malfunctions can occur
at the devices or the system itself.
• Only use a dv/dt filter compact that SIEMENS has released for operation with
NOTICE
Damage to the dv/dt filter compact by exceeding the maximum output frequency
The maximum permissible output frequency when using a dv/dt filter compact is 150 Hz.
The dv/dt filter compact can be damaged if the output frequency is exceeded.
• Operate the dv/dt filter compact with a maximum output frequency of 150 Hz.
14
CAUTION
attach a clearly visible and understandable warning notice at hazardous positions.
SINAMICS.
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 04/2014, A5E02590131A