NOTICE
Damage to the line filter through overheating when operated on the system without active
operation of the converter
Connection of the line filter to the supply system with no active converter operation can lead
to overload and damage to the line filter through overheating.
• Only connect the line filter to the supply system if the converter is active.
• Ensure that there is adequate cooling for the line filter.
Note
Disconnect the line filter for a high-voltage test
If a high-voltage test is conducted with alternating voltage in the system, the existing line
filters must be disconnected in order to obtain accurate measurements.
The connection clip to the interference suppression capacitor in the Power Module must also
be removed for a high-voltage test with direct voltage.
Assignment of line filter and Power Module
Table 2- 1
Assignment of line filter and Power Module
Power Module
6SL3310-1PE33-0AA0
6SL3310-1PE33-7AA0
6SL3310-1PE34-6AA0
6SL3310-1PE35-8AA0
6SL3310-1PE36-6AA0
6SL3310-1PE37-4AA0
6SL3310-1PE38-4AA0
6SL3310-1PE38-8AA0
6SL3310-1PE41-0AA0
6SL3310-1PG33-7AA0
6SL3310-1PG34-0AA0
6SL3310-1PG34-5AA0
6SL3310-1PG35-2AA0
6SL3310-1PG35-8AA0
6SL3310-1PG36-5AA0
6SL3310-1PG37-2AA0
14
Unit rating of the Power Module
Line voltage 380 – 480 V 3 AC
160 kW
200 kW
250 kW
315 kW
355 kW
400 kW
450 kW
500 kW
560 kW
Line voltage 500 – 690 V 3 AC
315 kW
355 kW
400 kW
450 kW
500 kW
560 kW
630 kW
Suitable line filter
6SL3000-0BE33-1AA0
6SL3000-0BE33-1AA0
6SL3000-0BE35-0AA0
6SL3760-0MR00-0AA0
6SL3760-0MR00-0AA0
6SL3760-0MR00-0AA0
6SL3760-0MR00-0AA0
6SL3760-0MR00-0AA0
6SL3760-0MR00-0AA0
6SL3760-0MS00-0AA0
6SL3760-0MS00-0AA0
6SL3760-0MS00-0AA0
6SL3760-0MS00-0AA0
6SL3760-0MS00-0AA0
6SL3760-0MS00-0AA0
6SL3760-0MS00-0AA0