Function Code 05H: Execute Operation - GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

8 COMMUNICATIONS
Modbus implementation:
GE Power Management implementation:
This function code allows the master to perform various operations in the 745. The 2 byte CODE VALUE of
FF00h must be sent after the OPERATION CODE for the operation to be performed.
MESSAGE FORMAT AND EXAMPLE:
Request to perform reset operation in slave device 11.
Master Query Message:
SLAVE ADDRESS
FUNCTION CODE
OPERATION CODE: high order byte
OPERATION CODE: low order byte
CODE VALUE: high order byte
CODE VALUE: low order byte
CRC: low order byte
CRC: high order byte
Field:
SLAVE ADDRESS
FUNCTION CODE
OPERATION CODE: high order byte
OPERATION CODE: low order byte
CODE VALUE: high order byte
CODE VALUE: low order byte
CRC: low order byte
CRC: high order byte
Table 8–2: SUMMARY OF OPERATION CODES FOR FUNCTION CODE 05H
OPERATION
DEFINITION
CODE
0000
NO OPERATION
0001
REMOTE RESET
0002
TRIGGER TRACE
MEMORY
0003
CLEAR MAXIMUM
DEMAND DATA
0004
CLEAR EVENT
RECORDER DATA
0005
CLEAR LOSS-OF-
LIFE DATA
0006
CLEAR TRACE
MEMORY
0007
CLEAR ENERGY
DATA
GE Power Management

8.2.10 FUNCTION CODE 05H: EXECUTE OPERATION

Force Single Coil
Execute Operation
Example (hex):
11
query message for slave 11
05
execute operation
00
remote reset
01
FF
perform operation
00
DF
6A
Example (hex):
11
response message from slave 11
05
execute operation
00
remote reset
01
FF
perform operation
00
DF
6A
DESCRIPTION
Does not do anything.
Performs the same function as the front panel RESET key.
Initiates a waveform capture of trace memory and increments the "Total Number
of Trace Triggers" registers.
Performs the same function as the command in message A2 METERING / DEMAND
/ DEMAND DATA CLEAR / CLEAR MAXIMUM DEMAND DATA.
Performs the same function as the command in message A3 EVENT RECORDER /
EVENT DATA CLEAR / CLEAR EVENT RECORDER DATA.
Performs the same function as the command in message S1 745 SETUP /
INSTALLATION / CLEAR LOSS-OF-LIFE DATA.
Clears all trace memory buffers and sets the "Total Number of Trace Triggers"
register to zero.
Performs the same function as the command in message A2 METERING / ENERGY /
ENERGY DATA CLEAR / CLEAR ENERGY.
745 Transformer Management Relay
8.2 MODBUS PROTOCOL