Download Print this page

Antenna Mounting - Siemens 563-004 Installation Instructions

Wireless field level network transceiver (flnx)

Advertisement

Document No. 563-002
Installation Instructions
January 12, 2007

Antenna Mounting

Direct Mount Antenna
The preferred mounting configuration is to mount
the FLNX outside the TEC enclosure in a location
where it will establish the maximum number of
communication links with other FLNXs and its
associated FPX. For example, in a VAV application
this will typically be on the bottom of the VAV box in
the ceiling plenum with the entire antenna extending
below the VAV box (Figure 2).
Figure 2. FLNX Mounting Options – No Enclosure.
Page 2 of 4
VAV BOX
VAV BOX
VAV BOX
Remote Mount Antenna
The FLNX is mounted inside the TEC (or any metal)
enclosure and the antenna is brought through a 1/2"
knockout (Figure 3).
The antenna extension cable is 12" long.
Figure 3. FLNX Mounted Inside Enclosure.
Installation
1. Determine the optimal location of the FLNX and
antenna for RF communications.
Ideally, the antenna should extend below the VAV
box.
2. Mount the FLNX using the provided screws.
You can also use double-sided tape or VELCRO
fasteners.
3. Set the Channel and Network ID switches to the
settings selected for the WFLN.
4. Connect the communication port of the FLN
device to the FLNX (cable length limit is 4000 ft).
5. Connect to 24 Vac power (Figure 4).
CAUTION:
If the FLNX shares the power supply
with a Wireless TEC Transceiver (TTX,
P/N 550-205) and the TEC, be sure to
use a ground isolated transformer (P/N
550-710) between the TTX and the power
transformer.