5.1. Parameter data

It is explanation by the reference method of the list of parameters of the VF-PS1 series as
follows. For communication purposes, see the parameter list on inverter's instruction
manual regarding the communication number, adjustment range and so forth.
<Example of excerpts from the inverter's instruction manual>
Communic
Title
ation No.
-
History function
auh
0000
Automatic
au1
acceleration/dec
eleration
0001
Automatic
au2
torque boost
Deceleration
0010
dec
time 1
Factory default
0007
typ
setting
*1: Default values vary depending on the capacity.
*2: Changing the parameter
(1)
"Title" means the display on the inverter panel.
(2)
"Communication number" is affixed to each parameter that is necessary for designating the
parameter for communication.
(3) "Adjustment range" means a data range adjustable for a parameter, and the data cannot be written
outside the range. The data have been expressed in the decimal notation. For writing the data through
the communication function, take the minimum setting unit into consideration, and use hexadecimal
system.
(4) "Minimum setup unit" is the unit of a single data (when the minimum unit is "-", 1 is equal to 1).
For example, the "minimum setup unit" of acceleration time (
For setting a data to 10 seconds, transmit 03E8h [10÷0.01=1000d=03E8h] by communication.
This option designs the unit of "Acceleration/deceleration time" in 0.1sec.
Please do not set "10:Acceleration/deceleration time setting 0.01 sec.~600.00sec".
in Factory default setting (typ=10).
A unit of "Acceleration/deceleration time setting" is changed instantly when set
typ=10.
Mandatory
When this option is connected to the inverter, the data unit of Point Number 31 and 32 is
changed to "0.01 second".
It is possible that it leads to the unexpected machinery operation, and death, a serious
wound or equipment parts are damaged.
Function
Adjustment range
0:Deselect
1:Automatic setting
2:Automatic setting (during
acceleration only)
0:Deselect
1:Automatic torque boost +
auto-tuning 1
0.1~6000 sec.
0: -
1:50 Hz default setting
2:60 Hz default setting
3:Factory default setting
10:Acceleration/deceleration
time setting 0.01
sec.~600.0 sec.
11:Acceleration/deceleration
time setting 0.1
sec.~6000sec.
enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).
Minimum
setting unit
(Panel/Communi
cation)
1/1
1/1
1/1
0.1/0.1 *2
1/1
Warning
- 20 -
E6581542①
Default
Write during
setting
running
-
-
Disabled
0
-
Disabled
Enabled
*1
-
Disabled
) is 0.01, and 1 is equal to 0.01s.
Refer
ence
5.1
5.2
5.3
5.2
5.20