Configuring Network Settings - Siemens AC5200 Quick Start Manual

Table of Contents

Advertisement

3.2

Configuring Network Settings

Siemens AB
Security Products
13. For each SR34i/SR35i upgraded, in the SiPass integrated bring up the Com-
ponent dialog and from the "ACC Controllers" item select "New Unit".
14. Select the Controller type as ACC-4, 8, 16, or 32, depending on the door
count.
15. Enter in the serial number saved from ACC-X startup screen and save it.
The ACC-X should connect to SiPass integrated shortly.
Make a note of the serial number and door count, and contact Logistics to pur-
chase an ACC-X Upgrade licence to make the upgrade permanent
Once your AC5200 is powered up and connected to the network, you will need to
configure the network settings and also note down the serial number.
To configure an AC5200:
1.
Open the AC5200 case if it is not already open
2.
Press 2 to modify Network Settings
3.
Press 2 to Change IP Settings
4.
Press 1 to set the IP Address
Enter the new IP address with the keypad
For numbers that are less than three digits add 0s in front, for example 001 or
016
Press any key except 1 to continue
5.
Press 2 to set the Subnet Mask
Enter the subnet mask with the keypad
Press any key except 1 to continue
6.
Press 3 to set the Gateway Address
Enter the gateway address with the keypad.
Press any key except 1 to continue
7.
Press 4 to set the Host Address. This is the IP address of your SiPass inte-
grated server PC
Enter the host address with the keypad.
8.
Press 5 to set the Port Address. This is the port the AC5200 uses to com-
municate with SiPass integrated. By default it is 4343
Enter the port address with the keypad.
9.
Press 1 to Apply Changes and Restart your AC5200
The AC5200 will restart with the entered network settings. You should see an Audit
Trail message in SiPass integrated indicating that the AC5200 is trying to connect.
AC5200 Configuration
13
10.2013