Basic Installation and Operation Guide
Fn #
Group
Function Description
F085
Fault History #1, Latest Fault
Time Stamp, Fault #1
F086
Based on F078-80
Date Stamp, Fault #1
F087
Based on F076-77
Fault History #2, Previous
F088
Fault
F089
Time Stamp, Fault #2
F090
Date Stamp, Fault #2
F091
Fault History #3, Oldest Fault
F092
Time Stamp, Fault #3
F093
Date Stamp, Fault #3
F094
Run Time, Hours
Run Time,
F095
1000 Hour Overflow
F096
Run Cycle Counter
Run Cycle Counter
F097
10K overflow
Function 51 Internal protection features
Several protection features in the TE Series are accomplished with internal hardware and use software
switches in Function 51 to enable or disable them. The following chart shows these functions and the
factory default settings. Refer to the Advanced Installation, Operation and Programming Manual,
Section 5.6.8.a for details on how to change these settings.
 
 
Protection
Function
 
 
Phase Rotation protection.
Phase Rotation
Phase rotation must match selection in Bit #2 below. Setting to Off (0) will make the TE
Trip
insensitive for use behind a reversing contactor
 
 
2 = A-B-C Phase Rotation Sequence Only
Expected Phase
Sequence
0 = A-C-B Phase Rotation Sequence Only
Phase Current
Phase Current Loss, any phase current reading is less than 8 - 20% (Depending on frame
Loss
size) of unit max amp rating after 3 seconds from Start command.
 
Shorted SCR
At least one SCR has shorted; there is no voltage drop across the SCR phase assembly.
Lockout
 
Shunt Trip of the main Circuit Breaker or Isolation Contactor (if provided and wired to an Aux.
Shunt Trip
relay in F060-F061)). 2 or more SCRs have shorted in opposing phases so current was
flowing to the motor while the TE was in the Off state.
PTC Input Trip
PTC Trip function. This can be disabled so that a jumper is not required across the PTC inputs.
 
Protection against loss of input line voltage. Disable when using an In-Line Isolation
Line Loss Trip
Contactor or any other system that normally removes line power from the starter. Resets
automatically when line voltage returns.
Table 6: Function 51 table of Hardware Protection Features
28 | P a g e
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
Adjustment / Display Range
0 = No fault history, or
Fault # 1 - 27: see Fault code list
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
01.01 – 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
0 = No fault history, or
Fault # 1 - 27: see Fault code list
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
01.01 – 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
0 = No fault history, or
Fault # 1 - 27: see Fault code list
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
01.01 – 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
000.0 – 999.9 hours
0000 – 9999 thousand hours
0000 – 9999 times
0000 – 9999 10 thousand times
Descriptio
n
Setting
Factory
Setting
Increments
Setting
1
0
00.01
00.00
00.01
01.01
1
0
00.01
00.00
00.01
01.01
1
0
00.01
00.00
00.01
01.01
0.1 hours
0
1 k-hour
0
1 times
0
1 10k times
0
Default
Setting
A-B-C
Rotation
 
Off
 
 
On
 
On
 
On
On
 
On