Commissioning

Introduction
You have configured and programmed the tunnel application. The following sections
describe how to commission the tunnel application.
Further information on commissioning is available in the system manual of Redundant
System S7-1500R/H (https://support.industry.siemens.com/cs/ww/en/view/109754833).
Inserting SIMATIC memory cards
Requirement:
The CPUs only support pre-formatted SIMATIC memory cards. If required, format the
SIMATIC memory cards before using them in the CPU.
Procedure: Insert a SIMATIC memory card into the left-hand CPU as follows.
1. Open the front cover of the CPU.
2. Ensure that the CPU is either switched off or in STOP mode.
3. Insert the SIMATIC memory card, as shown on the CPU, into the slot for the SIMATIC
memory card.
4. Carefully insert the SIMATIC memory card into the CPU, pushing gently, until the card
clicks into place.
5. Insert the other SIMATIC memory card into the right-hand CPU as described in steps 1 to
4.
Switching on load current supply and CPUs
Requirements:
The SIMATIC S7-1500R/H redundant system has been installed. The system has been
wired. The SIMATIC memory cards are in the CPUs. The load current supply is connected to
the power supply.
Procedure:
Turn on the load current supply.
Result:
● The CPUs run a flash test and on completion of system initialization goes to STOP. The
RUN/STOP LEDs on both CPUs are yellow.
● The two CPUs implement pairing. The ERROR LEDs are flashing red. In STEP 7 in the
diagnostic status (Online & diagnostics) of the S7-1500R/H system, check successful
paring. "Paired" is shown in the "Pairing state" field.
48
S7-1500R/H redundant system
Getting Started, 10/2018, A5E44910930-AA
4