Analog in 15 bit voltage/current 8ch

Advertisement

ANALOG IN 15 BIT VOLTAGE/CURRENT 8CH IC220ALG221
Local Diagnostic Indicators and Terminal Assignment
Figure 2
The ANALOG IN 15 BIT VOLTAGE/
CURRENT 8CH terminal
with an appropriate connector
Installation Instructions
High current flowing through potential jumpers U
jumpers and the internal temperature of the terminal to increase. Observe the following instructions
to keep the current flowing through the potential jumpers of the analog terminals as low as possible:
All of the analog terminals need a separate main circuit.
If this is not possible in your application and if you are using analog terminals in a main
circuit together with other terminals, place the analog terminals behind all the other
terminals at the end of the main circuit.
2
Local Diagnostic Indicators
Des.
Color Meaning
D
Green Bus diagnostics
Terminal Assignment for Each Connector
Terminal
Signal
Points
1.1
+U1
2.1
+U2
1.2
+I1
2.2
+I2
1.3, 2.3
-1, -2
1.4, 2.4
Shield
and U
causes the temperature of the potential
M
S
Assignment
Voltage input channel 1
Voltage input channel 2
Current input channel 1
Current input channel 2
Minus input (for both cur-
rent and voltage)
Shield connection