When using a single stage thermostat, second stage delay is based on the setting of
switch S1-1, S1-2 shown below.
Option Switches S1-1 & S1-2 Positions
Delay Time:
Off *
10 min
Auto min
20 min
Table 22 2nd Stage Delay For Single Stage Thermostats
* Factory default setting– two stage thermostat
2. Cooling Mode (if applicable)
In a typical single stage cooling system (Y connection), a call for cool is initiated by
closing the thermostat contacts. This energizes the compressor and the electronic
air cleaner (optional).
The circulator will be energized at cool speed after the COOL delay-to-fan-on
period. After the thermostat is satisfi ed, the compressor is de-energized and the
COOL delay-to-fan-off period begins. After the COOL delay-to-fan-off period ends,
the circulator and the electronic air cleaner are de-energized.
3. FAN Mode
If the thermostat fan mode is set to ON, the circulator fan (low heat speed) and
optional electronic air cleaner are energized. When the fan mode is returned to
AUTO, the circulator fan and electronic air cleaner (optional) are deenergized.

11.5 Gas Manifold Pressure Measurement and Adjustment

NOTICE:
To prevent unreliable operation or equipment damage,
the gas manifold pressure must be as specifi ed on the unit
rating plate. Only minor adjustments should be made by
adjusting the gas valve pressure regulator.
This valve is shipped from the factory with the regulator preset to 3.5 in. WC.
Consult the appliance rating plate to ensure burner manifold pressure is as
specifi ed. If another outlet pressure is required, follow these steps (see Table 23
and Fig. 37):
1.
Turn OFF all electrical power to the system.
2.
Using a 3/32 inch hex wrench, loosen outlet pressure tap screw one turn.
Do not remove screw.
3.
Attach a hose and manometer to the outlet pressure barb fi tting of valve to
overlap at least 3/8"
4.
Turn ON system power and set thermostat to a call for heat.
5.
Using a leak detection solution or non-chlorine soap suds, check for leaks at
hose connection. Bubbles forming indicate a leak. SHUT OFF GAS AND FIX
ALL LEAKS IMMEDIATELY!
6.
Remove burner access panel.
7.
Remove regulator screw cover. Turn regulator screw either clockwise to
increase pressure or counter clockwise to decrease. Always adjust regulator
to provide the correct pressure according to the original equipment
manufacturer specifi cations listed on the appliance rating plate.
Bosch Thermotechnology Corp. | 04.2019
On "S1" set switch #
1
2
Off
Off
On
Off
Off
On
On
On
8.
Replace regulator screw cover and fi nger-tighten securely.
9.
Turn OFF all electrical power to the system.
10.
Remove manometer and hose from outlet pressure tap.
11.
Tighten outlet pressure tap clockwise 7 in-Ibs minimum to seal port.
12.
Replace burner access panel.
13.
Turn ON system power and set thermostat to call for heat.
14.
Using a leak detection solution or non-chlorine soap suds, check for leaks at
hose connection. Bubbles forming indicate a leak. SHUT OFF GAS AND FIX
ALL LEAKS IMMEDIATELY!
MANIFOLD PRESSURE
TAP
INLET PRESSURE
TAP
ON/OFF SWITCH
COMMON TERMINALS (C)
Regulator
Cover
Screw
Regulator
Spring
Regulator
Sleeve
Figure 37
Gas valve and regulator adjustment
15.
Measure gas manifold pressure with burners fi ring. Adjust manifold
pressure per the Manifold Gas Pressure table.
Input
Rating
Furnace Model
Natural
KBTU/H
Gas
60
BGH96M060B3A
3.5" W.C
80
BGH96M080B3A
3.5" W.C
80
BGH96M080C4A
3.5" W.C
100
BGH96M100C5A
3.5" W.C
100
BGH96M100D5A
3.5" W.C
120
BGH96M100D5A
3.5" W.C
Table 23 Manifold Gas Pressure
The fi nal manifold pressure must not vary more than ± 0.3 in. WC from specifi ed
manifold pressure.
Any necessary major changes in gas fl ow rate should be made by changing the size
of the burner orifi ce.
Bosch 96% AFUE Gas Furnace | 45
HIGH FIRE
REGULATOR
ADJUSTMENT
REGULATOR VENT
LOW FIRE
REGULATOR
ADJUSTMENT
COAXIAL COIL
TERMINAL (M)
HIGH FIRE COIL TERMINAL (HI)
Plastic
Regulator
Adjustment
Screw
Range
Orifi ce Size
Propane
Natural
Propane
Gas
Gas
Gas
10" W.C
45
55
10" W.C
45
55
10" W.C
45
55
10" W.C
45
55
10" W.C
45
55
10" W.C
45
55