ABB COM600 Station Automation Series User Manual page 41

Dnp 3.0 lan/wan master opc 3.2
Hide thumbs Also See for COM600 Station Automation Series:
Table of Contents

Advertisement

1MRS756566
COM600 Station Automation Series
User's Guide
Property/ Para-
Value or Value range/ Default
meter
Subtype
Simple
Data Class Spe-
cific
Indication Object
Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
Scale and Unit
Multiplier
Default: Deka
Phase Number of
Default: 0
Decimals
Scale
Default: None
Unit
Default: Dimensionless
Limit Value Super-
vision
Max
Min
Table 3.4.8.16-2 Additional configurable properties for Sub-Type MV Limit Check
Property/ Para-
Value or Value range/ Default
meter
Sub-Type
MV Limit Check
Limit Value Super-
vision
High
Default: 0
High-High
Default: 0
Low
Default: 0
Low-Low
Default: 0
LAN/WAN Master
Description
MV Sub-type
Data object number for indication.
Specifies the multiplier for current SI unit.
Specifies the number of decimals shown
in HSI. (0..9)
Scale to be used with this type
SI unit for measurement as described in
IEC61850
Maximum value for measurement
Minimum value for measurement
Description
MVSubTypeDescription
High limit for measurement. Event is cre-
ated when value crosses the limit.
High-high limit for measurement. Event is
created when value crosses the limit.
Low limit for measurement. Event is cre-
ated when value crosses the limit.
Low-low limit for measurement. Event is
created when value crosses the limit.
DNP 3.0
(OPC) 3.2
41

Advertisement

Table of Contents
loading

Table of Contents