Digital Input/Output Modules
8.4.9
6ES5 441-4UA13/4UA14 Digital Output Module
Rated supply voltage L+
Number of outputs
Isolation
Range for supply voltage
Fusing
Output voltage
for logic 1
for logic 0
Switching current (resistive, inductive load)
Residual current at logic 0
Switching current for lamps
Switching frequency
with resistive load
with inductive load
Breaking voltage (inductive)
Total switching current
Coincidence factor (total load capability)
ventilated
not ventilated
Permissible line length
Power supply
Digital section from system bus
Current consumption from L+/L–
Power dissipation (rated operation)
Enable input (F+/F–)
Rated input voltage
Input voltage
for logic 1
for logic 0
Rated input current
Permissible line length
Short-circuit monitoring
Indicator for signaling output (H+)
Output voltage
referred to L– (with feed at 1L+)
for logic 1
for logic 0
Switching current
Mechanical specifications
Dimensions (W x H x D)
Weight
1)
Short-circuit protection responds with line resistance
8-48
–4UA13
–4UA14
24 V DC
1)
32, short-circuit protected
no
20 to 30 V DC
6.3 A slow,
7 A, fast, 1 fuse per 8 out-
1 fuse per 8 outputs
puts
L+ -1.5 V min.
3 V max.
5 mA to 0.5 A
0.5 mA max.
0.22 A max. (5 W)
100 Hz max.
2 Hz max. at 0.3 A, 0.5 Hz max. at 0.5 A
Limited to L+ – 47 V
Limited to L+ –55 V
4 A max. per 8 outputs
100 %
o
50 %; 100 % up to 35
C
400 m max. unshielded
5 V, 80 mA typical
24 V, 150 mA typical
24 V, 200 mA typical
17.0 W
6.4 W
24 V DC
13 to 33 V
– 33 to 5 V
5 mA
200 m max.
Red LED for every 8 outputs
1L+ – 5 V min.
1L+ –1.5 V min.
3 V max.
3 V max.
10 mA max., limited
20 mm x 255 mm x 195 mm
Approx. 0.45 kg
15 ohms, irrelevant for the –4UA14 .