Bosch CLIMATE 5000 VRF RDCI Series Installation Manual page 7

All dc inverter outdoor units
Hide thumbs Also See for CLIMATE 5000 VRF RDCI Series:
Table of Contents

Advertisement

12 ST3.9 self-threading screws
411
213
411
411
213
411
1250
Curve diagram of static pressure, air flow volume.
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
12500
12000
11500
11000
10500
10000
9500
0
5
10
Static pressure (Pa)
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
13500
13000
12500
12000
11500
11000
10500
0
5
10
Static pressure (Pa)
14/16HP
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
/h)
3
15500
15000
14500
14000
13500
13000
12500
0
5
10
Static pressure (Pa)
RDCI Series – All DC Inverter Outdoor Units
Remove the fan grills
Fig. 4-22
10
12-Ø3.2
Fig. 4-23
8/10HP
15
20
25
Fig. 4-24
12HP
15
20
25
Fig. 4-25
15
20
25
Fig. 4-26
OUTDOOR UNIT INSTALLATION | 7
Example B
C
1210
A
Radius
B
Air outlet louver dimension (optional)
725
Ø3.2
411
213
411
411
213
411
1250
Table.4-5
Unit: mm
A
A≥300
B
B≥250
C
C≤3000
D
750≤D≤760
θ
θ≤15°
NOTE
Before installing the air deflector, please ensure the fan grill has
been taken off.
Once air deflector has been installed, the air volume, cooling/
heating capacity will decrease. The maximum angle allowed for the
shutter is 15 degrees.
Only one bend set is allowed.
Install anti vibration pads in between the unit and air deflector.
Support
Fig. 4-27
12 ST3.9 self-threading screws
Remove the fan grills
Fig. 4-28
Fig. 4-29
Table.4-6
Unit: mm
A
A≥300
B
B≥250
C
C≤3000
θ
θ≤15°
6 720 862 437 (2016/10)