Process Value - Toshiba TOSVERT VF-S15 Instruction Manual

Pid control
Hide thumbs Also See for TOSVERT VF-S15:
Table of Contents

Advertisement

It is possible to set or switch the forward/ reverse characteristics.
a) Example of setting reverse characteristic
f217
(60Hz)
f219
(0Hz)
b) Example of switching characteristic by S3 input terminal (positive logic)
f219
(60Hz)
f217
(0Hz)
Title
f116
Input terminal selection 6 (S3)
f216
VIC input point 1 setting
f217
VIC input point 1 frequency
f218
VIC input point 2 setting
f219
VIC input point 2 frequency

4.1.2. Process value

Input the target value in relation to the feedback value as process value.
1. Select the process signal at f389.
Description
fmod / f207 selected
Terminal VIA
Terminal VIB
fpid
RS485 communication
UP/DOWN from external logic input
CANopen communication
Communication option
Terminal VIC
Pulse train input
It is possible to add or multiply for process value by override function.
Parameter setting
(Converted frequency)
4mA
20mA
f216
f218
Parameter setting
(Converted frequency)
20mA
4mA
f216
f218
20%
100%
Function
S3 terminal OFF
S3 terminal ON
*When switching the characteristics using
terminals, not only characteristics of process
value but also of feedback value switches.
Example of setting
54: PID characteristics switching
20(%)
0(Hz)
100(%)
60(Hz)
PID control reference signal selection (f389)
11
E6581879
0
1
2
3
4
5
6
7
8
11