Huawei SmartLogger2000 User Manual page 115

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000
User Manual
No. Parameter
14
Arc detection
adaptation
mode
15
AFCI self-test
16
Current error
during scanning
17
OVGR linked
shutdown
Dry contact
18
function
19
Hibernate at
night
Issue 04 (2018-04-10)
Description
Adjusts the sensitivity of
arc detection.
Send the AFCI self-test
command manually.
When the IV curves of PV
strings are being scanned,
the current change of PV
strings operating properly
should be monitored to
avoid inaccurate scanning
caused by sunlight
change. If the current
exceeds the specified
value, it is determined that
the sunlight changes, and
the IV curves should be
scanned again.
If this parameter is set to
Enable, the inverter shuts
down after receiving the
OVGR signal. If this
parameter is set to
Disable, the inverter does
not shut down after
receiving the OVGR
signal.
Identifies the dry contact
signals from the
SmartLogger.
The inverter monitors PV
strings at night. If
Hibernate at night is set
to Enable, the monitoring
function of the inverter
will hibernate at night,
reducing power
consumption.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
N/A
High
Moderate
Low
N/A
N/A
A
[0.00, 2.00]
N/A
Disable
Enable
N/A
NC
OVGR
N/A
Disable
Enable
7 WebUI
Remarks
This parameter is supported
by the inverters named with
-US and displayed when
AFCI is set to Enable.
N/A
This parameter is displayed
after the Japanese grid code
is selected.
Set this parameter to OVGR
for OVGR signals, and set it
to NC for other signals. This
parameter is displayed after
the Japanese grid code is
selected.
N/A