5 EXCLUSION ZONES

An exclusion zone is defined as the minimum distance
permitted between instrumentation devices and the point
where EMI/RFI emitters may be activated. Within an exclusion
zone, the activation of e.g. handheld two-way radios is
prohibited.
As a general rule, transmitting devices must always be
operated at least 'an arms length' away from any
instrumentation.
Administrative controls should be used to establish exclusion
zones in specified areas where instrumentation and control
systems have been installed and are operational.
Exclusion Zone
60
55
50
45
40
35
30
25
20
15
10
5
0
0.5
1
1.5
Notes.
• 10V/m corresponds to the CE mark testing field strength limit standard.
• 4V/m corresponds to the NRC 8dB de-rating of the 10V/m field strength limit.
Fig. 5.1 EMI Field Strength (Volts/Meter) vs Distance (Feet) vs Radiated Power (Watts)
4
EMI Field Strength vs Distance vs Radiated Power
10W
8W
5W
4W
2W
2
2.5
3
3.5
4
4.5
The size of the exclusion zone(s) should be site-specific and
dependent upon the effective radiated power of the portable
EMI/RFI emitter type(s) likely to be used.
Some examples of exclusion zone distances recognized by
European Industry standards (for CE marking), and by the
U.S. Nuclear Regulatory Commission (NRC) are shown in
Figure 5.1 below.
Table 5.1 shows some examples of relationships between
radiated power, distance and EMI field strength, derived from
the graphs in Figure 5.1.
R
a
d
a i
e t
d
P
o
w
O
u
p t
u
( t
W
a
t t
5
2
1
0
5 .
1W
0.5W
5
5.5
6
6.5
7
Feet
r e
1
0
/ V
m
D
s i
a t
n
c
e
) s
F (
e
e
) t
4
0 .
2
5 .
1
8 .
1
3 .
7.5
8
8.5
9
9.5
4
/ V
m
D
s i
a t
n
c
e
F (
e
e
) t
1
0
0 .
6
4 .
4
5 .
3
2 .
10 V/m Limit
4 V/m Limit
10

Advertisement

loading