Universal Controller -
3 Section
ZA-10006-YAD
Issue a : 5/11/96
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See 'Fault Finding'.
Fault Finding:
Set-up Unit does not reach the first
screen.
•
If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
•
There may be a controller with the same
name, already logged on the network.
•
There may be a maximum 32 controllers
already on the network segment.
•
Check on the InTouch panel, P.C. or
Supervisor.
Display Alarm Messages:
AL
Temperature alarm
Ft
Probes 1 and 2 are faulty
LA
Log probe alarm
Pn
probe 'n' faulty or not connected
(Where 'n' = probe number)
EE
EEPROM fault
rr
Internal program fault
E1
Plant fault 1
E2
Plant fault 2
ES
Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Parameter
Cut in Temperature
Differential Below
Control Weight
Display Weight
Section 1: OT Alarm
Section 1: UT Alarm
Section 2: OT Alarm
Section 2: UT Alarm
Section 3: OT Alarm
Section 3: UT Alarm
Alarm Delay
Latch Alarm: 0=Off ; 1=On
Defrost Start
Number of Defrosts per Day
No Defrost Time
Section 1: Defrost Term. Temp.
Section 2: Defrost Term. Temp.
Section 3: Defrost Term. Temp.
Defrost Minimum Time
Defrost Maximum Time
Defrost Min. Recovery Time
Defrost Max. Recovery Time
Drain Down Time
Defrost Alarm Temp.
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas
Defrost Mode: 0=Local ;
1=Remote
Defrost Hold: 0=Off ; 1=On
Pulse Defrost: 0=Off ; 1=On
Hour
Minute
Day
Month
Year
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
Lights/Blinds: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
Polarity: 0=N/O ; 1=N/C
Sunday (Blinds) Up / Down
Monday Up / Down
Tuesday Up / Down
Wednesday Up / Down
Thursday Up / Down
Friday Up / Down
Saturday Up / Down
Gas Alarm: 0=Off ; 1=On
Minor Leak
Major Leak
Manual Defrost: 0=Off ; 1=On
Comments:
DIN
Range/Units
0
-49 to 30 / °C
1
0 to 30 / °C
2
0 to 100 / %
3
0 to 100 / %
44
-49 to 60 / °C
45
-49 to 60 / °C
47
-49 to 60 / °C
48
-49 to 60 / °C
50
-49 to 60 / °C
51
-49 to 60 / °C
17
00:00 to 99:00/Min:Sec
18
0 to 1
4
00:00 to 23:59/Hrs:Mins
5
0 to 6
6
0 to 25 / Hrs.
46
-49 to 60 / °C
49
-49 to 60 / °C
52
-49 to 60 / °C
7
00:00 to 99:00/Min:Sec
8
00:00 to 99:00/Min:Sec
9
00:00 to 99:00/Min:Sec
10
00:00 to 99:00/Min:Sec
11
00:00 to 20:00/Min:Sec
12
-49 to 60 / °C
13
0 to 2
14
0 to 1
15
0 to 1
16
0 to 1
19
0 to 23
20
0 to 59
21
0 to 31
22
0 to 12
23
0 to 99
24
0 to 2
25
0 to 3
26
0 to 1
27/28
00:00 to 23:59/Hrs:Mins
29/30
00:00 to 23:59/Hrs:Mins
31/32
00:00 to 23:59/Hrs:Mins
33/34
00:00 to 23:59/Hrs:Mins
35/36
00:00 to 23:59/Hrs:Mins
37/38
00:00 to 23:59/Hrs:Mins
39/40
00:00 to 23:59/Hrs:Mins
41
0 to 1
42
0 to 3500 / ppm.
43
0 to 3500 / ppm.
99
0 to 1
Default
Dsgn
Act.
HT(LT)
0 (-20)
1.5 (2)
50
50
5 (-16)
-2 (-25)
5 (-16)
-2 (-25)
5 (-16)
-2 (-25)
20:00
0
01:00
6
7
10
10
10
05:00
24:00
(25:00)
20:00
30:00
01:30
20
0
0
0
0
0
0
0
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
0
50
200
0
YAD08t / 65EAEE