11.2 Pulse Type and Value
The pulse outputs provided by the E-Mon Class 3400 Meter are watt-hours and
var-hours. Output 1 is the watt-hour pulse and Output 2 is the var-hour pulse.
The pulse value is dependent on the amperage size of the meter. See the chart
below for the values also true for expansion board pulse output.
Meter Amps
100
200
400
800
1600
3200
NOTE: The standard pulse option is not functional when used with the
expanded feature package.
Fig. 24. E-Mon Class 3400 Meter Standard Watt-hour Pulse Output.
Watt-hours / pulse
1.95313
3.90625
7.8125
15.625
31.25
62.5
SELECTION PINS 1 AND
2 FOR WATT-HOURS VIA
3 POSITION JUMPER J43
THE WATT-HOUR OUTPUT
IS THE 2 POSITION TERMINAL
BLOCK HERE
47
E-MON CLASS 3400 METER
Var-hours / pulse
1.95313
3.90625
7.8125
15.625
31.25
M34374
62.5
62-0398—02