Connector / Terminal
X6 / 4.7
X6 / 4.6
X6 / NC
X6 / NC
In module AI523, the signals I8-, I10-, I12- and I14- are internally connected to an analog earth.
The potential difference of the analog earth to M is ±1 V (max.). The replacement device does
not have current sources on pins 35 and 36. If necessary, these current sources can be con-
nected to individual measurement channels via the configuration (DIP switch).
Fig. 59: Differential voltage input
1) Electrically isolated power supply of analog sensor
2) Earthing at sensor
±10 V or ±5 V at differential inputs
On the replacement devices, the wire-break detection is also active in case of a differential
voltage measurement. For this purpose, each measuring channel is internally pulled to "plus" by
means of a high-impedance resistor. As a result, the individual potentials of the differential
voltage measurement must also be referenced to M. Completely isolated voltages are not sym-
metrized to M by the inputs.
2018/09/24
Pin
33
34
35
36
CAUTION!
System damage caused by voltage!
The exchange of a replacement device under voltage can cause permanent
system damage (destruction).
The potential difference of the earthing at the sensor to M must not be too big
± 1 V for the whole signal range). Otherwise problems can occur con-
(max.
cerning the common-mode input voltages of the involved analog inputs.
3ADR010122, 8, en_US
Replacement devices: I/O modules > Replacement device 07AI91-AD