Configuring A Pulse Channel For Pwm - Siemens S7-1200 System Manual

Hide thumbs Also See for S7-1200:
Table of Contents

Advertisement

PWM3
PTO4
PWM4
1
2
3
8.6.3

Configuring a pulse channel for PWM

To prepare for PWM operation, first configure a pulse channel in the device configuration by
selecting the CPU, then Pulse Generator (PTO/PWM), and choose PWM1 through PWM4.
Enable the pulse generator (check box). If a pulse generator is enabled, a unique default
name is assigned to this particular pulse generator. You can change this name by editing it
in the "Name:" edit box, but it must be a unique name. Names of enabled pulse generators
will become tags in the "constant" tag table, and will be available for use as the PWM
parameter of the CTRL_PWM instruction.
Table 8- 150 CPU output: maximum frequency
CPU
1211C
1212C
1214C and 1215C
1217C
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
Description
Built-in outputs
SB outputs
Built-in I/O
SB I/O
Built-in outputs
SB outputs
The CPU 1211C does not have outputs Q0.4, Q0.5, Q0.6, or Q0.7. Therefore, these outputs
cannot be used in the CPU 1211C.
The CPU 1212C does not have outputs Q0.6 or Q0.7. Therefore, these outputs cannot be used in
the CPU 1212C.
This table applies to the CPU 1211C, CPU 1212C, CPU 1214C, CPU 1215C, and CPU 1217C
PTO/PWM functions.
CPU output channel
Qa.0 to Qa.3
Qa.0 to Qa.3
Qa.4, Qa.5
Qa.0 to Qa.4
Qa.5 to Qb.1
DQa.0 to DQa.3
(.0+, .0- to .3+, .3-)
DQa.4 to DQb.1
Pulse
Q0.4
1
Q4.1
Q0.6
2
Q4.2
Q0.6
2
Q4.3
Pulse and direction
output
100 kHz
100 kHz
20 kHz
100kHz
20 kHz
1 MHz
100 kHz
Extended instructions
8.6 Pulse
Direction
-
-
Q0.7
2
Q4.3
-
-
A/B, quadrature, up/down,
and pulse/direction
100 kHz
100 kHz
20 kHz
100kHz
20 kHz
1 MHz
100 kHz