Technical specifications
Article number
Power
Power available from the backplane bus
Power loss
Power loss, typ.
Digital outputs
Number of digital outputs
Current-sinking
Current-sourcing
Short-circuit protection
Controlling a digital input
Switching capacity of the outputs
on lamp load, max.
•
Output current
for signal "1" rated value
•
for signal "1" permissible range, min.
•
for signal "1" permissible range, max.
•
for signal "0" residual current, max.
•
Parallel switching of two outputs
for logic links
•
for uprating
•
for redundant control of a load
•
Switching frequency
with resistive load, max.
•
with inductive load, max.
•
on lamp load, max.
•
Total current of the outputs
Current per channel, max.
•
Current per group, max.
•
Current per module, max.
•
Relay outputs
Number of relay outputs
•
Rated supply voltage of relay coil L+ (DC)
•
Current consumption of relays (coil current
•
of all relays), typ.
external protection for relay outputs
•
Contact connection (internal)
•
Size of motor starters according to NEMA,
•
max.
Number of operating cycles, max.
•
Relay approved acc. to UL 508
•
26
6ES7522-5HH00-0AB0
0.8 W
5 W
16
Yes
Yes
No
Yes
50 W (230 V AC), 5 W (24 V DC)
2 A
10 mA; 10 V
2 A; thermal continuous current
0 A
Yes
No
Yes
1 Hz
0.5 Hz
1 Hz
2 A; see additional description in the manual
4 A; see additional description in the manual
32 A; see additional description in the manual
16
24 V
150 mA
Miniature circuit breaker B10 / B16
No
5
see additional description in the manual
No
Digital output module DQ 16x230VAC/2A ST Relay (6ES7522-5HH00-0AB0)
Manual, 07/2017, A5E34934019-AC