Supplemental Specifications; Actuator Travel; Housing; Transmission Data And Contributing Factors - ABB PositionMaster EDP300 Operating Instruction

Digital positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D

14 Supplemental specifications

Actuator travel

Rotation angle
Used range
25 ... 270° for rotary actuator
25 ... 60° for linear actuator
Actuator travel limit
Min. and max. limits, freely configurable in
range 0 ... 100 %
Actuator travel (min. range > 20%
Actuator travel time
Range of 0 ... 200 seconds, separately for each
prolongation
direction
Dead band time limit
Setting range 0 ... 200 seconds (monitoring
parameter for control until the deviation
reaches the dead band)

Housing

Material / Degree of protection
Aluminum with
0.1% copper Optional stainless steel 1.4404 (316L)
Degree of protection
IP 65 / NEMA 4X (NEMA 4X does not permit
overhead mounting)
Surface / color (aluminum housing only)
Dipping varnish
With epoxy resin, stove-hardened
Housing varnished black
RAL 9005
RAL 9002
Weight
Aluminum
2.4 kg (5.29 lb)
Stainless steel 1.4404 (316L)
5.5 kg (12.13 lb)
Mounting orientation
Any
Transmission data and contributing
factors
Output Y1
Increasing set point signal
Decreasing set point signal
Action (set point signal)
Increasing set point
Decreasing set point
Characteristic curve (actuator travel = f {set point signal})
Linear
Equal percentage 1:25 or 1:50 or 25:1 or 50:1*
Deviation
< 0.5 %
Configurable zone
0 to 100 %,
Configurable dead zone
0.1 to 10 %,
Resolution (AD-conversion)
> 16,000 steps
Sampling frequency
20 ms
Ambient temperature effect
< 0.5 % for each 10 K
Influence of vibration
Standard design:
Marine version:
*
freely configurable with 20 reference points

Seismic vibration

Meets requirements of DIN / IEC 60068-3-3 Class III for strong
and strongest earthquakes.

Influence of mounting orientation

Not measurable.

Noise emissions

Max. 100 db (A)
Noise-reduced version max. 85 db (A)
Increasing pressure at output
Decreasing pressure at output
= actuator position 0 to 100 %
= actuator position 0 to 100 %
< 1 % to 10 g and 80 Hz
< 1 % to 4 g and 100 Hz – EDP300 and
remote design (control unit) < 1 % to 10 g
and 100 Hz for remote design (position
sensor)
79
0 to 100 %
0 to 100 %
4 to 20 mA
20 to 4 mA

Hide quick links: