Cable Entries; Dimensions, Weights And Noise - ABB ACS800-U7 Hardware Manual

Acs800 45 to 560 kw; 50 to 600 hp
Hide thumbs Also See for ACS800-U7:
Table of Contents

Advertisement

122

Cable entries

Mains, motor and brake resistor cable terminal sizes (per phase), maximum
accepted cable and tightening torques are given below.
Frame
size
Number of
holes per
phase
1)
R5
2)
R6
R7
R8
1)
external brake resistor (+D150) and DC connection terminals: wire size 6...70 mm
tightening torque 15 Nm
2)
external brake resistor (+D150) and DC connection terminals: wire size 95...185 mm
tightening torque 40 Nm

Dimensions, weights and noise

Frame size
R5
R6
R7
R8
1)
in marine applications (+C121) extra height: 10 mm from the fastening bar at the bottom of the
cabinet
2)
extra width for units with brake resistors (+D151): SAFURxxxFxxx 400 mm, 2xSAFURxxxFxxx
800 mm, 4xSAFURxxxFxxx 1600 mm
3)
extra width for units with EMC filter (+E202): 200 mm
4)
extra width for units with EMC filter (+E202): 400 mm
5)
in marine applications (+C121) depth with fastening bars: 700 mm
Technical data
L1, L2, L3, U2, V2, W2, UDC+/R+, UDC-, R-
Hole
Max. wire
diameter
size
mm
mm
1
60
185
1
60
185
3
60
1×240 or
2×185
3
60
3×240
Height
IP21/22/42
mm
2130
2130
2130
2130
Screw
Tightening
2
M10
M10
M12
M12
1)
2)
Width
IP54
mm
mm
2315
430
2315
430
3)
2315
830
4)
2315
830
Earthing PE
Screw
torque
Nm
20...40
M10
20...40
M10
50...75
M10
50...75
M10
2
5)
Depth
Weight
mm
kg
689
300
689
300
689
400
689
500
Tightening
torque
Nm
30...44
30...44
30...44
30...44
, screw M8,
2
, screw M10,
Noise
dB
63
63
71
72
00184674 -J

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-07

Table of Contents