Siemens RDD100.1RF Operating Instructions page 2

Hide thumbs Also See for RDD100.1RF:

Advertisement

Are your rooms too warm/too cold?
+
+
Press
or
to increase or decrease the room
temperature setpoint in increments of 0.5 °C/1 °F.
Proceed as follows:
+
Press
or
Press
to save the setting or wait for the
program to exit automatically
To permanently change the temperature
setpoints, use parameters P05 and P07.
To lock the setpoints, use parameters P06 and
P08
Does symbol
appear on the display?
Symbol
is displayed when the batteries are low. Replace
them with 2 new alkaline batteries type AAA. Proceed as
follows:
Get 2 new alkaline batteries type AAA
Remove the battery holder and then the batteries. Insert the
new batteries and, within 1.5 minutes, replace the battery
holder
Ensure the exhausted batteries are disposed of correctly, in
compliance with environmental requirements
Do you want to pair transmitter and receiver?
Please refer to the instructions that come with the RDE-MZ6.
2/2
Operating Instructions
to change the setpoint temporarily.
CB1B1431en_01 / 2013-07-05
Do you want to change parameters?
+
If you want to change control parameters, proceed as
follows:
+
Press
and
Release them and parameter P02 is displayed
+
Press
or
to be changed
Press
to select the parameter
+
Press
or
Press
to confirm and save the changed value
Select and change other parameters
The program automatically returns to the normal
screen after a timeout
Parameter list
Parameter
Description
no.
P02
Selection of °C or °F
P03
Standard temperature
display
P04
Temperature sensor
calibration
P05
Comfort setpoint
P06
Comfort setpoint lock
P07
Economy setpoint
P08
Economy setpoint lock
P09
Buzzer
P10
Show frost protection
icon
P19
Sequential number of
room unit
P20
RF learn
P21
Scanning rate for the
capacitive buttons
Note: Shorter
scanning rate means
shorter battery life
P22
Reload factory
settings
P23
Software version
information
simultaneously for 5 seconds
to scroll to the parameter that needs
to change the value
Setting range (default)
1 = °C (default)
2 = °F
1 = room temperature
(default)
2 = setpoint
-3...3 °C
Step 0.5 °C
(-6...6 °F, step 1 °F)
Default: 0 °C
5...35 °C, step 0.5 °C
(41...95 °F, step 1 °F)
Default: 20 °C, 68 °F
0 = OFF (default)
1 = ON  locked according
to setting in P05
5...35 °C, step 0.5 °C
(41...95 °F, step 1 °F)
Default: 16 °C, 61 °F
0 = OFF (default)
1 = ON  locked according
to setting in P07
0 = OFF
1 = ON (default)
0 = OFF (default)
1 = ON and always on at 5 ºC
0 = no display of zone
(RF off)
1 = zone number 1
(for standard RF) (default)
6 = zone number 6
0 = OFF (default)
1 = ON
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
0 = OFF (default)
1 = reload
No adjustment possible