GE 169 Instruction Manual page 48

Motor management relay
Table of Contents

Advertisement

3 SETUP AND USE
Table 3-3 SETPOINTS
3$*(
,1)250$7,21 /,1(
1
PAGE 1: SETPOINTS VALUES
MOTOR AMPS SETPOINTS
1
PHASE CT RATIO
SECONDARY = X AMP
1
PHASE CT RATIO
CT RATIO = XXXX:x
1
MOTOR FULL LOAD CURRENT
FLC= XXXX AMPS
1
ACCEL.TIME= XXX.X SECONDS
Consult motor data sheet
1
STARTS/HOUR= X
Consult motor data sheet
1
UNBALANCE ALARM LEVEL
U/B ALARM= XX PERCENT
1
U/B ALARM TIME DELAY
TIME DELAY = XXX SEC
1
UNBALANCE TRIP LEVEL
U/B TRIP= XX PERCENT
1
U/B TRIP TIME DELAY
U/B DELAY= XXX SECONDS
1
G/F CT RATIO :5 ? XXX
(NO indicates 2000:1)
1
G/F CT RATIO
G/F CT = XXX:5
1
GROUND FAULT ALARM LEVEL
G/F ALARM= XXX AMPS
1
G/F ALARM TIME DELAY
TIME DELAY = XXX SEC
1
GROUND FAULT TRIP LEVEL
G/F TRIP = XXX AMPS
5$1*(
:1 or :5
20-1500 (increments of 1)
10-1500 amps (increments of 1)
0.5-125.0 or OFF (increments of 0.5)
1-5 starts or OFF (increments of 1)
4-30 % or OFF (increments of 1)
3-255 seconds (increments of 1)
4-30 % or OFF (increments of 1)
3-255 seconds (increments of 1)
YES (5 amp secondary) or NO (2000:1)
50-250 (increments of 50)
(Not seen if ratio is 2000:1)
2000:1 CT: 1.0-10.0 amps or OFF (steps of 1.0)
5 A secondary CT: 10-100% of primary amps or
OFF (increments of 10%)
1-255 seconds (increments of 1)
2000:1 CT: 1.0-10.0 A or OFF (steps of 1.0)
5 A secondary CT: 10-100% of primary amps or
OFF (increments of 10% )
42
g
GE Power Management
0$18$/ 5()
3.10
3.10
3.10
3.10
3.7
3.7
3.7
3.8
3.9
3.11
3.11
3.11
3.11
3.11