Series 2200 and 3200 Relative Humidity
and Temperature Room Units
Product Description
These room units measure relative humidity and
temperature in the occupied space in which they are
installed. Models with display allow users to view the
measured temperature value. A version with
temperature setpoint adjustment is also offered.
The effective sensing range is 32°F to 122°F (0°C to
50°C), and the setpoint range is 55°F to 95°F (13°C
to 35°C). The humidity measuring range is 0 to
100% RH.
Hardware is included for installation on drywall or on
a 2" × 4" electrical box.
Product Numbers
QFA3212.FWxN
QFA3212.EWxN
QFA3232.EWxN
Accessories
AQA2200-INTL
Room Unit Back Plate
(10-pack)
563-102 GSKT KIT
Room Sensor Insulating
Gasket (10-pack)
(For hollow wall installations)
Caution Notations
CAUTION
Item Number 129-104, Rev. JA
QFA32SS.FWxN
QFA32SS.EWxN
Equipment damage or loss of
data may occur if you do not
follow a procedure as
specified.
Installation Instructions
Expected Installation Time
20 minutes
Required Tools
·
Sizes 1 and 2 Phillips screwdrivers
·
Small and medium flat-blade screwdrivers
·
1/16-inch hex key
·
Medium-duty electric drill
·
3/16-inch (4.8 mm) drill bit
·
One-inch (25 mm) hole saw
·
Small level
·
Tape measure
·
Marker or pencil
Prerequisites
·
Review these instructions before beginning.
·
Installed: appropriate field wiring within the
maximum wiring run length for the individual
equipment controller. The maximum
recommended length is 750 feet (229 m) for
18 AWG; 300 feet (91 m) for 22 AWG.
·
All wiring must comply with National Electric
Code (NEC) and local regulations.
Figure 1. Typical Temperature Room Unit.
Document No. 129-104
December 11, 2017
Page 1 of 4