SERVICE CONDITIONS
Application Condition
The type HCV vacuum contactor is manufactured in accordance with IEC 60470 (1974), NEMA ICS 3 Part 2
(1993). The vacuum contactor should be used in the following conditions.
- Altitude:
-Ambient temperature:
-Relative humidity:
-Vibration:
-Shock
-Weight
If the contactor is to be used in conditions other than those specified above, please consult Toshiba
International Corporation.
System
0.8PF Ind/Syn
Voltage
2.2-2.5kV
1750HP
3.0-3.3kV
2250HP
4.0-5.0kV
3000HP
6.0-6.6kV
4500HP
The above table is based on general load data and standard application. Lower limitations may apply on
specific applications (i.e. applications above 6600 feet elevations).

Location condition

The location where the contactor is to be installed should be free from dust, corrosive gas and moisture.
When it is to be used in a chemical plant or in outdoor applications, take necessary precautions against
corrosion, water seepage and condensation.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Table 1
Normal Service Conditions
Table 2
General Application and Load Data
1.0PF Syn Motor
Motor
2000HP
2500HP
3500HP
5000HP

GENERAL DESCRIPTION

Less than 2,000 m
(6600 ft)
Above 2,000 m consult factory
-5°C min. to +40°C max.
Its average over a period of
24 hr does not exceed +35°C.
45% min. to 85% max.
20 Hz - 1G or less
43 lbs.
Latched type 44 lbs.
3 Phase
3 Phase Capacitor
Transformer
1500kVA
2000kVA
3000kVA
4000kVA
30G
1500kVAR
2000kVAR
2000kVAR
2000kVAR