Table 3: Single Zone Vertical Air Handling Unit Electrical Data
Model Number
Nominal Tons
LV180HV4
1-1/2
LV240HV4
2
LV360HV4
3
LV420HV
3-1/2
LV480HV
4
Voltage tolerance is ±10%.
Maximum allowable voltage imbalance is 2%.
MSC = Maximum Starting Current.
Compressor
Compressor
Qty
(A) Cool / Heat
1
13.5/13.5
1
13.5/13.5
1
21/21
1
21/21
1
21/21
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Outdoor Unit
Fan Qty
Fan (A)
1
1.6
1
1.6
2
1.6/1.6
2
1.6/1.6
2
1.6/1.6
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
GENERAL DATA
Electrical
MCA (A)
MOP (A)
20
20
32
32
32
30
30
40
40
40
11