RO1A, RO1B, RO1C, RO2A, RO2B, RO2C. Warning! The ACS 400 is not a field repairable unit. Never attempt to repair a broken unit; contact the factory or your local Authorized Service Center for replacement.
Step by step instructions The installation of the ACS 400 has been broken down in a number of steps that are listed on page 2. The steps must be carried out in the order shown. At the right of each step reference is made to one or more Reference Sections on the following pages of this User’s Manual.
Page 12
TURN the power on. See N Figure 1 Step by step instructions for installing the ACS 400. The references after each step refer to one or more of the Reference Sections on the following pages in this manual. ACS 400 User’s Manual...
• Relative humidity less than 95% (non-condensing) The ACS 400 must be installed in a heated, indoor controlled environment that is suitable for the selected enclosure. Drives are available in either an IP21/NEMA1 or an IP54/NEMA12 enclosure. The drive must be protected from airborne dust, corrosive gases or liquids, and conductive contaminants such as condensation, carbon dust, and metallic particles.
C Mounting the ACS 400 on a Wall Warning! Before installing the ACS 400 ensure the input power supply to the drive is off. The lid of the packing-box provides a Wall Mounting Template. Remove the lid from the box.
3 Lift the other retaining lever e.g. with a screwdriver. 4 Open the upper part of the front cover and remove it. Figure 9 Opening the frame size R3 and R4 size drives of type IP 21/ NEMA 1. ACS 400 User’s Manual...
Page 18
IP 54/NEMA 12 1 Take the screws off. 2 Remove the front cover. 3 Remove panel if needed. Figure 10 Opening type IP 54 / NEMA 12 drives. ACS 400 User’s Manual...
Figure 11 Terminal Interface. F Attaching a Warning Sticker The contents of the packing box include warning stickers in different languages. Attach a warning sticker in the language of your choice on the inside plastic shell as indicated above. ACS 400 User’s Manual...
I2n/I2nnd 48...63 Hz Ser.no. *1982800001* For more information see ACS400 User’s Manual 0...250Hz Figure 12 ACS 400 type designation label. AC S 4 0 1 AC Drive Product Type S = Standard industrial drive ACS 400 Product Family Input Bridge...
A package, containing five screws and two cable clamp brackets, is included with the type IP 54 / NEMA 12 ACS 400 drives. These are required only for IEC installations. Gland plates are used for IEC installations and conduit plates are used for US installations. Contact your local ABB representative for additional information regarding IEC installations.
Page 22
Figure 18 Installing the gland plate for control cables (B), type IP 21 / NEMA 1 drives. The conduit plate is attached with three screws into threaded holes marked a in Figure 16 and b in Figure 17. ACS 400 User’s Manual...
Refer to Section S Specifications for current, ratings, fuse recommendations and the maximum wire size capacities and tightening torques for the terminals. The ACS 400 is suitable for use on a circuit capable of delivering not more than 65,000 RMS symmetrical amperes, 480 V maximum. The ACS 400 has an electronic motor protection feature that complies with the requirements of the National Electric Code (USA).
Digital input common for DI1, DI2 and DI3. To activate a digital input, there must be ≥+10 V 10 DCOM1 (or ≤-10 V) between that input and DCOM1. The 24 V may be provided by the ACS 400 (X1:9) using the connection examples (see Section L) or by an external 12-24 V source of either polarity.
(See Sections G and S). Warning! Ensure the motor is compatible for use with the ACS 400. The ACS 400 must be installed by a competent person. If in doubt, contact your local ABB sales or service office. ACS 400 User’s Manual...
1. Replace the control panel. 2. Replace the front cover. N Applying Power When power is applied to the ACS 400, the green LED comes on. Note! Before increasing motor speed, check that the motor is running in desired direction. O Environmental Information The package is made of corrugated cardboard and can be recycled.
Note! Whenever the ACS 400 detects a fault condition, the fault relay activates. The motor stops and the ACS 400 will wait to be reset. If the fault still persists and no external cause has been identified, contact your local ABB sales or service office.
If the motor current I exceeds nominal current I of the motor for a prolonged period, the ACS 400 automatically protects the motor from overheating by tripping. The trip time depends on the extent of the overload (I ), the output frequency and f .
95 (heat sink) Power 10, AWG6 16, AWG4 35, AWG2 Terminals*** (stranded) (stranded) (stranded) Torque Torque Torque 1.3-1.5Nm 1.5-1.8Nm 3.2-3.7Nm Control Terminals 0.5 - 1.5 (AWG22...AWG16)/Torque 0.4 Nm LIne fuse ****3~ Power Losses Power Circuit 79.2 Control Circuit ACS 400 User’s Manual...
Page 31
80%. ***** Maximum cable lengths listed are based on capacitive coupling between motor wires and from motor wires to ground. It may also be necessary to consider motor insulation requirements related to drive output dv/dt. ACS 400 User’s Manual...
**** Fuse type: UL class CC or T. ° Use 60°C rated power cable (75°C if T above 45 T Product Conformity The ACS 400 complies with European requirements: • Low Voltage Directive 73/23/EEC with amendments • EMC Directive 89/336/EEC with amendments Corresponding declarations and a list of main standards are available on request.
U Accessories ACS 100-PAN Control panel for use with the ACS 100 / ACS 140 / ACS 400. ACS-PAN-A Control panel for use with the ACS 400. ACS 100-EXT Extension cable kit for use with the control panel. ACS400-IF11-3 through ACS400-IF41-3 RFI input filters.
Control Modes The first time the drive is powered up, it is controlled from the Control Terminal Strip X1 (remote control, REM). The ACS 400 is controlled from the control panel when the drive is in local control (LOC). Switch to local control (LOC) by pressing and holding the LOC/REM button until first LOCAL CONTROL or LOCAL, KEEP RUN is displayed: •...
The reference can be modified in local control mode or in remote control mode depending on programming. Menu Structure The ACS 400 has a large number of parameters. Of these, only the basic parameters are initially visible. See “Selecting Full Parameter Set” on page 28 for details on specifying the full parameter set.
Note! To view the parameter default value while in the parameter set mode, press the UP/ DOWN buttons simultaneously. Adjust the Panel Display Contrast Simultaneously depressing the ENTER key and the UP/DOWN key will adjust the display contrast. ACS 400 User’s Guide...
Removal and reapplication of power automatically alters the menu to the short parameter set.. Press & hold FULL/SHORT MENU FULL/SHORT MENU ENTER MENU MENU Visible if full menu is active. ACS 400 User’s Manual...
Note! If no other button is pressed within 15 seconds and the fault is still active, the fault code will be displayed again. After a power failure, the drive will revert to the same control mode (LOC or REM) as before the power failure. ACS 400 User’s Guide...
The first time the drive is powered up, it is controlled from the Control Terminal strip (remote control, REM). The ACS 400 is controlled from the control panel when the drive is in local control (LOC). Switch to local control (LOC) by pressing and holding the MENU and ENTER buttons down simultaneously until first Loc or later LCr is displayed: •...
OUTPUT Menu Structure ACS 400 has a large number of parameters. Of these, only the basic parameters are initially visible. The menu function -LG- is used to make the full parameter set visible. See “Select between basic and full menu” on page 33.
Resetting the Drive from the Control Panel When the red LED of the ACS 400 is on or blinking, a fault is active. To reset a fault when the red LED is on, press the START/STOP button. Caution! This may start the drive, when in remote control.
Diagnostics The ACS 400 alarms and faults are described in Table 5 and Table 6 respectively. The ACS100-PAN control panel displays only the alarm and fault codes. The alarm and fault messages are displayed only by the ACS-PAN-A control panel.
Page 46
Panel loss. Panel is disconnected when Start/Stop/Dir or reference is coming from panel. See parameter 3002 and APPENDIX. Note! If FL10 is active when the power is turned off, the ACS 400 will start in remote control (REM) when the power is turned back on.
ACS 400 Basic Parameters The ACS 400 has a large number of parameters. Of these, only the basic parameters are initially visible. Setting up only a few basic parameters is sufficient for applications where the preprogrammed application macros of the ACS 400 can provide all desired functionality. For a full description of programmable features provided by the ACS 400, see “ACS 400 Complete Parameter List”, starting...
Page 49
Note! Analog output content is programmable. Values given here are valid only if other analog output configuration parameters have not been modified. Description of all parameters is given in “ACS 400 Complete Parameter List” starting on page 51. Group 20 LIMITS 2003 MAX CURRENT Maximum output current.
Page 50
Default value: 1 ( LINEAR Group 33 INFORMATION 3301 SW VERSION Software version code. S = Parameters which can be modified only when the drive is stopped. ACS 400 User’s Guide...
Default values of certain parameters depend on the selected macro. These are listed with the description of each macro. Default values for other parameters are given in “ACS 400 Complete Parameter List” starting on page 51.
RO2A Default: Running =>20 connected to 22 RO2B *Note! DI 4 is used to configure ACS 400. It is read only once when power is connected. When DI 4 is open (0) the following applies: • All parameters marked * are determined by the DI4 input.
AI2: • Ramp pair 1/2 selection (DI5) • Relay output 2: Running *Note! DI 4 is used to configure ACS 400. It is read only once when power is connected. When DI 4 is connected (1) the following applies: •...
AO CONTENT MAX 1002 1601 COMMANDS NOT SEL RUN ENABLE NOT SEL 1003 1604 DIRECTION REQUEST FAULT RESET SEL KEYPAD 2008 50 Hz MAXIMUM FREQ 1102 2105 PREMAGN SEL NOT SEL 1103 2201 5 (DI5) EXT REF SELECT ACS 400 User’s Manual...
AO CONTENT MAX 1002 1601 COMMANDS NOT SEL RUN ENABLE NOT SEL 1003 1604 DIRECTION REQUEST FAULT RESET SEL KEYPAD 2008 60 Hz MAXIMUM FREQ 1102 2105 PREMAGN SEL NOT SEL 1103 2201 EXT REF SELECT NOT SEL ACS 400 User’s Manual...
AO CONTENT MAX 1002 1601 COMMANDS NOT SEL RUN ENABLE NOT SEL 1003 1604 DIRECTION REQUEST FAULT RESET SEL KEYPAD 2008 50 Hz MAXIMUM FREQ 1102 2105 PREMAGN SEL NOT SEL 1103 2201 EXT REF SELECT ACS 400 User’s Manual...
AO CONTENT MAX 1002 1601 COMMANDS NOT SEL RUN ENABLE NOT SEL 1003 1604 DIRECTION REQUEST FAULT RESET SEL KEYPAD 2008 50 Hz MAXIMUM FREQ 1102 2105 PREMAGN SEL NOT SEL 1103 2201 EXT REF SELECT NOT SEL ACS 400 User’s Manual...
Output frequency 0...20 mA <=> 0...50 Hz AGND +24 VDC +24V DCOM1 Start/Stop: Activate to start ACS 400 (Hand). Forward/Reverse: Activate to reverse rotation direction (Hand) EXT1/EXT2 Selection: Activate to select auto control Forward/Reverse (Auto) Start/Stop: Activate to start ACS 400 (Auto)
ACS 400 Complete Parameter List Initially, only the basic parameters (shaded grey in Table 7) are visible. See “Selecting Full Parameter Set” on page 28 for menu function to select full parameter set. S = Parameters can be modified only when the drive is stopped.
Page 62
1302 0 - 100 % 100 % MAXIMUM AI 1303 0 - 10 s 0.1 s 0.1 s FILTER AI 1304 0 - 100 % MINIMUM AI 1305 0 - 100 % 100 % MAXIMUM AI ACS 400 User’s Manual...
Page 63
0 - 250 s 0.1; 1 s STOP DC INJ TIME á á 2105 0 - 6 PREMAGN SEL 2106 0.0 - 25.0 s 0.1 s 2.0 s PREMAGN MAX TIME 2107 0 - 1 START INHIBIT ACS 400 User’s Manual...
Page 64
0.5 - 50 Hz 0.1 Hz 20 Hz STALL FREQ HI 3012 10...400 s 20 s STALL TIME 3013 0 - 2 UNDERLOAD FUNC NOT SEL 3014 10...400 s 20 s UNDERLOAD TIME 3015 1 - 5 UNDERLOAD CURVE ACS 400 User’s Manual...
Page 65
3407 102 - 137 P VAR 3408 1 - 9999 P VAR MULTIP 3409 1 - 9999 P VAR DIVISOR 3410 0 - 3 P VAR SCALING 34011 0 - 31 3 (Hz) P VAR UNIT ACS 400 User’s Manual...
Page 66
0 - FFFF PARITY ERRORS 5211 0 - FFFF CRC ERRORS 5212 0 - FFFF BUSY ERRORS 5213 0 - 255 SER FAULT MEM 5214 0 - 255 SER FAULT MEM 5215 0 - 255 SER FAULT MEM ACS 400 User’s Manual...
9902 APPLIC MACRO Application macro selection. This parameter is used to select the Application Macro which will configure the ACS 400 for a particular application. Refer to “Application Macros”, starting page 41 , for a list and description of available Application Macros.
See “APPENDIX”, starting page 115 , for description of different control locations. 0114 RUN TIME (R) Shows the total run time of the ACS 400 in thousands of hours. Can be reset by pressing UP and DOWN buttons simultaneously when in parameter set mode. 0115 kWh COUNTER (R) Shows the ACS 400 operating hours.
Page 69
0135 PROCESS VAR 2 Process variable 2, as selected by parameters in group 34. 0136 RUN TIME Shows the total running time of ACS 400 in thousands of hours (kh). 0137 MWh COUNTER Counts the megawatt hours of ACS 400 in operation.
The Start/Stop and Direction commands are given through serial communication. *Note! In cases 1, 3, 6 direction is set with parameter 1003 . Selecting value 3 ( DIRECTION REQUEST fixes direction to Forward. **Note! Stop signal must be activated before Start command can be given. ACS 400 User’s Manual...
Page 71
Rotation direction lock. This parameter allows you to fix the direction of rotation of the motor to forward or reverse. If you select 3 ( ), the direction is set according to the given direction command. REQUEST ACS 400 User’s Manual...
External control location 2 ( 2) is selected. The control signal sources for 2 are defined with parameter 1002 (Start/Stop/Direction commands) and parameter 1106 (reference). COMM External control location 1 or 2 is chosen through serial communication. ACS 400 User’s Manual...
Page 73
Minimum reference for joystick should be 0.3 V ( 0.6 mA) or higher. If a 0 ... 10 V signal is used, the ACS 400 will operate at maximum reference in the reverse direction if the control signal is lost. Set parameter 1301 AI1 to a value 0.3 V or higher, and parameter 3001...
Page 74
• If the PID Control macro is selected, this parameter sets the maximum process reference. • If any other macro than PID Control is selected, this parameter sets the maximum frequency reference. This value is given as percentage of maximum frequency. ACS 400 User’s Manual...
Page 75
EXT REF MINIMUM EXT REF MAXIMUM by parameters 1301 and 1302 or parameters 1304 and 1305, depending on the analog input used. Example: For 4 to 20 mA input, set 1301 = 20% and 1302 = 100%. ACS 400 User’s Manual...
Group 12: Constant Speeds The ACS 400 has 7 programmable constant speeds, ranging from 0 to 250 Hz. Negative speed values cannot be given for constant speeds. Constant speed selections are ignored if the drive is in local mode or if the process PID reference is followed (see PID Control Macro).
1305 MAXIMUM AI2 Maximum value of AI2 (%). Value corresponds to maximum reference set by parameter 1105 EXT REF or 1108 EXT REF 1306 FILTER AI2 Filter time constant for AI2. Refer to parameter 1303 FILTER AI ACS 400 User’s Manual...
Relay is not used and is de-energized. READY The ACS 400 is ready to function. The relay is energized unless no run enable signal is present or a fault exists and supply voltage is within range. Relay energized when the ACS 400 is running.
Page 79
Code Description 21 = ACS OVERLOAD Relay is energized when ACS 400 overload alarm or fault exists. 22 = UNDERVOLTAGE Relay is energized when undervoltage alarm or fault exists. 23 = AI1 LOSS Relay is energized when AI1 signal is lost.
Minimum output current. 1505 MAXIMUM AO Maximum output current. 1506 AO FILTER Filter time constant for AO. AO (mA) 1505 1504 AO content 1503 1502 AO (mA) 1505 1504 AO content 1503 1502 Figure 25 Analog output scaling. ACS 400 User’s Manual...
1...5 = DI1 ... DI5 To activate the run enable signal, the selected digital input must be activated. If the voltage drops and deactivates the selected digital input, the ACS 400 will coast to stop and not start until the run enable signal resumes.
Code Description 2003 MAX CURRENT Maximum output current. The maximum output current that the ACS 400 will supply to the motor. The default value is 1.5 * I 2005 OVERVOLT CTRL DC overvoltage controller enable. Fast braking of a high inertia load causes the DC bus voltage to rise to the overvoltage control limit. To prevent the DC voltage from exceeding the limit, the overvoltage controller automatically decreases the braking torque.
Group 21: Start/Stop The ACS 400 supports several start and stop modes, including flying start and torque boost at start. DC current can be injected either before the start command ( 1... 5) or right after PREMAGN SEL the start command (...
- 0). MAXIMUM FREQ 2206 RAMP SHAPE Acceleration/deceleration ramp shape selection LINEAR FAST S CURVE MEDIUM CURVE SLOW S CURVE Output frequency MAXIMUM FREQ Linear S curve Time Ramp time Figure 26 Definition of acceleration/deceleration ramp time. ACS 400 User’s Manual...
Group 25: Critical Freq In some mechanical systems, certain speed ranges can cause resonance problems. With this parameter group, it is possible to set up to two different speed ranges that the ACS 400 will skip over. Code Description 2501 CRIT FREQ SEL Critical frequencies activation.
Motor acoustical noise option tandard (switching frequency 4 kHz). ow noise (switching frequency 8 kHz). Note! When the low noise setting is used, the maximum overload of the ACS 400 is I 30 °C ambient temperature or 0.9 * I at 40 °C.
CONST SPEED LAST SPEED A warning indication is displayed and the speed is set to the level the ACS 400 was last operating at. This value is determined by the average speed over the last 10 seconds. Caution: If you select...
Page 88
FAULT Displays a warning indication at 95 % of the nominal value. Displays a fault indication when the motor temperature reaches 100 % level. The ACS 400 coasts to stop. WARNING A warning indication is displayed when the motor temperature reaches 95 % of the nominal value.
Page 89
NOT SEL Stall protection not used. FAULT When the protection is activated the ACS 400 coasts to stop. Fault indication is displayed. WARNING A warning indication is displayed. The indication disappears in half the time set by parameter 3012 STALL...
Page 90
3007 have default values. CURVE ZERO SPEED LOAD 70 % 50 % 30 % 2.4 * ƒ ƒ ƒ Figure 33 Underload curve types. T nominal torque of the motor, nominal frequency of the motor. ACS 400 User’s Manual...
3101 NR OF TRIALS 3103 DELAY TIME This parameter sets the time that the ACS 400 will wait after a fault occurs before attempting to reset. If set to zero, the ACS 400 will reset immediately. 3104 AR OVERCURRENT...
1 (1402 RELAY OUTPUT RELAY OUTPUT value is SUPRV OVER SUPRV OVER B = Parameter 1401 1 (1402 RELAY OUTPUT RELAY OUTPUT 2)value is SUPRV UNDER SUPRV UNDER Figure 35 Operating data supervision using relay outputs. ACS 400 User’s Manual...
Group 33: Information Code Description 3301 SW VERSION Software version. 3302 TEST DATE Displays the test date of the ACS 400 (yy.ww). ACS 400 User’s Manual...
18 = MWh 22 = bar 26 = cFm 30 = Cst2 3 = Hz 7 = rpm 11 = mA 15 = kWh 19 = m/s 23 = kPa 27 = ft 31 = Fpm ACS 400 User’s Manual...
Page 95
P VAR DIVISOR Since variable 0103 is displayed with 0.1 Hz resolution, it is internally scaled so that OUTPUT FREQ value 10 represents 1 Hz. Therefore, Parameter 3405 must be set to (1). P VAR SCALING ACS 400 User’s Manual...
Group 40: PID Control The PID Control Macro allows the ACS 400 to take a reference signal (setpoint) and an actual signal (feedback), and automatically adjust the speed of the drive to match the actual signal to the reference. The control signal block diagram is show in figure 34 on page 118 of the Appendix.
Page 97
4008 ACT2 INPUT SEL Source for actual value 2 ( 1 = AI 1 Analog input 1 is used as actual value 2. 2 = AI 2 Analog input 2 is used as actual value 2. ACS 400 User’s Manual...
Page 98
Analog input signal AI min AI max Figure 38 Actual value scaling. The range of the analog input signal is set by parameters 1301 and 1302 or parameters 1304 and 1305, depending on the analog input used. ACS 400 User’s Manual...
Page 99
Code Description 4013 PID SLEEP DELAY Time delay for the sleep function, see Figure 39. If the ACS 400 output frequency is below a set level (parameter 4014 ) longer than , ACS 400 is stopped. SLEEP LEVEL PID SLEEP DELAY 4014 PID SLEEP LEVEL Level for activation of sleep function, see Figure 39.
CONST SPEED LAST SPEED A warning indication is displayed and the speed is set to the level the ACS 400 was last operating at. This value is determined by the average speed over the last 10 seconds. Caution: If you select...
5208 BUFFER OVERRUNS Longest possible message length for the ACS 400 is 32 bytes. If a message exceeding 32 bytes is received, this diagnostic counter increases by one every time a character is received and cannot be placed in the buffer.
Page 103
BUSY ERRORS In Modbus network, only one device can transmit at any given time. This diagnostic counter increases by one every time the ACS 400 receives a character from the bus while it is still processing the previous message. 5213 SER FAULT MEM Last Modbus exception code sent.
Channel 1 is the standard Modbus fieldbus connection. Communication settings of Channel 1 can be configured by the user. To control the ACS 400 via Modbus, the ACS 400 must be programmed to accept control commands and/or frequency references from Channel 1. Channel 0 is reserved for drive control panels ACS-PAN and ACS100-PAN, and for the Drive Window PC tool.
Page 106
Data Flow Fieldbus Master (PLC) Fieldbus Figure 41 Structure of a fieldbus system. ACS 400 User’s Manual...
Termination should not be done on the intermediate stations. See Figure 42 for the proper method of termination . Terminated Terminated Figure 42 Termination for the RS485 link. Warning! The connections should only be made with the drive disconnected from the power source. ACS 400 User’s Manual...
(given in Table 12), making parameter read and write possible. The following sections describe how to configure the ACS400 for more sophisticated communication and control. Table 12 Default communication settings of the Channel 1. Communication Station number Parity bit Stop bits speed 9600 bps none ACS 400 User’s Manual...
COMMUNICATION and 52 STANDARD MODBUS. Default communication settings for Channel 1 are listed in Table 12. To be able to communicate with the master device, the ACS 400 must use the same communication speed and parity settings as the master.
The ACS 400 drive can receive control information from multiple sources, including digital I/O, analog I/O, keypad, and Modbus fieldbus. To control the ACS 400 via the serial communication channel 1 (Modbus fieldbus), it must be programmed to accept control commands and/or frequency references from this channel. To accept control from serial communications, ACS 400 must be in remote control.
Page 111
Selects the source of the run enable RUN ENABLE NOT SEL COMM 1... signal. COMM 1604 Fault reset source FAULT RESET SEL KEYPAD ONLY COMM 1... Note! Fault reset is always possible START STOP with conrol panel. COMM ACS 400 User’s Manual...
It is possible to control both the relay outputs 1 and 2, as well as the analog output from the serial communication channel 1. Relay outputs can be controlled in the following way: Step 1: Configure the ACS 400 to supervise the value of any of the parameters 131-133 using parameters in group 32 SUPERVISION Step 2: Configure a relay output 1 or 2 to respond to the status of one of the supervised parameter.
Page 113
102 - 137 e.g. 133 Directs the contents of parameter 133 to AO CONTENT the analog output. 1503 Analog output scaling: upper limit (20 mA) AO CONTENT MAX reached when value 255 written to parameter 133. ACS 400 User’s Manual...
Typical physical interface is RS485. Modbus is designed for integration with Modicon PLCs or other automation devices, and the services closely correspond to the PLC architecture. The ACS 400 drive ‘looks like’ a Modicon PLC on the network. If detailed information regarding the Modicon Modbus protocol is required, contact your local ABB sales office for a copy of Modbus Protocol Guide.
The register addresses between the groups are invalid. No reads or writes are allowed for these addresses. If there is an attempt to read or write outside the parameter addresses, the Modbus interface will return an exception code to the controller. ACS 400 User’s Manual...
Function Codes The ACS 400 supports the Modbus function codes given in Table 20. If any other function codes are used ACS 400 returns an exception response with error code 01 (illegal function). Table 20 Function codes.
The Control Word Holding register: 40001 The Control Word is the principal means for controlling ACS 400 from a fieldbus system. It is sent by the fieldbus master station to the drive. ACS 400 switches between its states according to the bit-coded instructions on the Control Word.
Reference 1 Holding Register: 40002 Reference 1 can be used as the frequency reference 1 for the ACS 400. Scaling: 20000 (Hz, parameter 1105). Scaling Parameter 1104 is not used. EXT REF The signal source of external reference 1 (...
The Status Word Holding Register: 40004 The Status Word is a read-only word containing information of the ACS 400 status. The contents of Status Word is presented in the following table. The text in italics refers to the states in Figure 43.
ACCELERATOR ENABLED Step 5 CW = 0000 0000 0011 1111 When this value is written, the ramp function generator (RFG) input is released. Drive will accelerate to the given reference. State machine state changes to OPERATING ACS 400 User’s Manual...
Page 122
(e.g. digital input). State I = Output current CW = Control Word f = Output frequency SW = Status Word RFG = Ramp Function Generator Figure 43 The state machine for evaluation of start and stop signals. ACS 400 User’s Manual...
Fault and Alarm Status The ACS 400 provides fault and alarm status words that are accessible only from the serial communication link (not from the control panel). These status words are located in place of parameter group 3 (Modbus holding registers 40301- 40309).
Page 124
Undervoltage controller alarm Direction lock alarm Serial communication loss Modbus exception generated locally Analog input 1 loss Analog input 2 loss Panel loss ACS 400 overtemperature Motor overtemperature Underload Motor stall alarm DDCS link Reserved Reserved ACS 400 User’s Manual...
1 (Hz) or KEYPAD REF SEL 2 (%). If 1 (Hz) is selected, the type of reference is frequency and it is given to the ACS 400 in Hz. If 2 (%) is selected, the reference is given in percent.
Remote Control When the ACS 400 is in remote control (REM), the commands are given primarily through digital and analog inputs, although commands can be given also through the control panel or serial communication. Parameter 1102 selects between the two external control locations...
Page 127
Start/Stop Local NOT SEL REQUEST DI1-DI5 Direction Remote FORWARD NOT SEL KEYPAD DI1-DI5 REVERSE Enabled, KEYPAD DI1-DI5 RUN ENABLE DIRECTION COMMANDS COMMANDS 1003 1601 1001 1002 Figure 46 The control signal connections of the ABB Standard, Alternate and Premagnetize macros.
Page 128
EXT REF CONST EXT REF KEYPAD SELECT SPEED SEL SELECT REF SEL 1102 1103 1201 1106 1101 Control Terminals Analog KEYPAD inputs Remote Min freq Remote Max freq Digital KEYPAD Local Local inputs Crit. sp. Const. Applic DI1-DI5 speeds Acc/Dec ACTUAL 2 (%) INPUT SEL...
Page 129
ABB Drives & Power Products 16250 W. Glendale Drive New Berlin, WI 53151 Telephone (414) 785-8378 (800) 243-4384 (414) 780-5135...