Line voltage.....................33 Line termination element (Application see chapter 9.2)......33 Compatibility (detector <–> line type) .............33 Important components ................34 Programming switch ”S3”................34 Connections ....................35 Connection "Collective" SynoLINE600/-Ex ..........36 E3M111 Line module ”SynoLOOP”.............37 Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Page 4
E3L030 Control module VdS ..............60 15.1 Overview ....................60 15.2 Application....................60 15.3 Key data ....................60 15.4 Important components ................61 15.5 Programming switch ”S3”................62 15.6 Special functions ..................62 15.7 Connections ....................63 E3G050 Control module ”Contacts” ...........64 Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
About this document Purpose This document describes the function of hardware modules of the control unit FC700A. The consistent adherence to these instructions is a prerequisite for a safe application. Scope This document contains information for all modules FC700A, valid for all software versions.
Page 8
Disregard of the safety regulations Before they are delivered, products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or disregard of warnings of danger contained in the documentation.
The symbols listed below indicate the nature and origin of the danger. Signal word General danger Signal word Electrical voltage Example for a danger warning DANGER Disconnect the module from power supply. External voltage Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
This espe- cially applies when switching-off system components. In the case of extinguishing systems, always use the ”General installation in- structions” as a guideline. This guideline is available on request. Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Page 11
Batteries require environmentally safe disposal. They must be handed in at the local collecting points. Please take into account that the extinguishing agent cylinders are pressurized and must be exchanged in compliance with the local safety regulations. Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
SynoLINE600 SynoLOOP SynoLINE600-Ex B3Q580/ B3Q590/ Control modules I-Bus E3G050 E3L020 E3G070 E3L030 E3G060 Treiber 1..16 1...8 1..6 Z3B171 Z3B171 250V 250V FBF FSD ÜE FÜ Fire control Fire control installations installations Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Page 13
Remote transmission equipment Fire department control panel (VdS ’D’) Fire department key cabinet (VdS ’D’) ÜE Transmission device (VdS ’D’) 3rd party products not listed in this document, see chapter 15 Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Page 14
B3R051 30VDC / 1A Printer Gateway FG700A B3D021 C-Bus FT700A E3I020 RS232 E3H020 Building Management System (ISO1745 protocol) Power supply with accessories Mains FC700A Batteries B2F020 E3C011 AX12.. 29,6V/6A B3Q700 I-Bus Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Page 15
Printer Module Specification E3I020 RS232 module Gateway Module Specification E3H020 C-Bus Gateway module Power supply with accessories Module Specification B2F020 Converter 115/230V 29,6V / 6A as system voltage E3C011 Battery-charging module Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
– Emergency operation circuit at C-Bus level (external) Comprises the functions ”Collective alarm” and ”Silence alarm horns” – Requires 3 additional wires between FC700A and FT700A – The line ’Emergency operation circuit fire alarm’ is electrically monitored – Function ’Monitoring’ must, if not used, be set to inactive (SWE700A) –...
Operation also in emergency mode (= 3 additional wires for emergency operation between CPU and control consoles) Second de-coupled 24V supply (= 3 additional wires if there is no autono- mous power supply) Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Page 18
Emergency operation circuit and the emergency power supply are not laid out as a loop line – Route emergency power supply in a separate cable or in the C-Bus cable feedback – Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
The basic FM requirement is to safely monitor and detect ground faults, of all lines leaving the panel. The FC700A has been technically adjusted to fulfil those requirements. For FM installations, adhere the FM Approval mark to the control unit housing next to APPROVED the type label.
- If galvanically isolated relays are used, make sure that the 3rd party system takes over the ground fault monitoring function. Ground fault monitoring reacts if the resistance is: a) 4k from positive potential to ground, or ≤ Ω 16k from negative potential (system ground) to ground ≤ Ω Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
- for the connection of the prefabricated cable for battery, temperature sensor and power unit E3C011 Battery terminals (+, -, Centre tap) Temperature sensor Card chassis - mounted on module chassis Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
FG... ”S2” is set to variant 11 (ALARMCOM) at the factory Floating charge voltage as a function of temperature, or for diagrams of the various types of battery see page 25 Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
The I-Bus address setting is given as default by the tool (SWE700A) as address 16, therefore the programming switch 'S3' of the E3C011 must be set accordingly. Floating charge voltage as a function of temperature Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products...
Page 26
E3C011 Battery charging module Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
LED ”Power supply fault” external voltage Input voltage > 31.0V → power unit malfunction – – EEPROM check sum error LED ”Power on” – Input voltage > 28.5V LED ”Battery fault” – no function Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
2) Function "24V external voltage" or "without battery" can be programmed via maintenance PC With the function "external voltage", battery presence monitoring can be programmed as "active" (i.e. the external voltage is monitored). Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products...
Parallel operation Switches on primary side With metal shielding Dimensions 200 x 100 x 40 Power supply general The power supply for fire control unit FC700A consists of the following three com- ponents: Converter B2F020 – Battery-charging module E3C011 –...
Check mains voltage setting before commissioning The converter is supplied by the factory at 230V To switchover to 115V remove metal shield (remove screws ) and then plug in jumper at the ”115V ” pin Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Batteries larger than 27Ah per E3C011 are impossible if the recharging of a bat- – tery is to be done according to regulations (to 80% capacity within 24h) See page 20 for interconnection principle – Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
4,5mA during AI ”dark” phase Line voltage limit 26,5 ... 27,7V Quiescent line current max. 4,5mA Reset time 3 sec. Turn-on alarm delay 4.6 sec. Fault delay 15 sec. Module quiescent current at 24V 85mA Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
20V Ex detectors (without restrictions) used via DC1192 with SB3: DO1101-Ex, DT110x-Ex Line termination with Line type 1 Special detectors: DLO1191, (with mixed lines also OP620C, HI62xC, DM110x, DC1192) EOL22 (Ex) Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus devices. Function / I-Bus address Programming switch S3 S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 Module out of commission (unused) I-Bus user number ”S3-1...6” are set to ”off” at the factory Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus modules Data communication I-Bus modules to other I-Bus modules 1) Local ground connection 2) To read in technical alarms. Do not mix with detectors on the same line Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
According to EN54, a ”simple error” may not cause the malfunction of more than 32 detectors. After the short circuit the line automatically reverts to ”Normal operating condition”. Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products...
I-Bus devices. Function / I-Bus address Programming switch S3 S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 Module out of commission (unused) I-Bus user number ”S3-1...6” are set to ”off” at the factory Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus module E3G070 Plug-in terminals blue Supply for blue I-Bus modules to other I-Bus module green Double flat cable header from I-Bus module E3G070 Data communication I-Bus modules to other I-Bus module Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
30V/1A EB322A AB322A 30V/1A free terminals CO NC NO CO NN 4k75 4k75 rear end APMK Load factor for addressable elements SynoLOOP (limited by 128 per loop) Details see document 007836 Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus address is set at programming switch ”S3” Only one module per station possible 11.2 Application Required for all LON applications within FC700A, such as: LON-I/O p.c.b. K3I110 – LON/Mimic Display converter K3I050 with Mimic display drivers K3R072 (or –...
EOL resistor R60 on E3I040 has to be changed to 50Ω (e.g. use 2 resistors of 100Ω in parallel circuit). T-taps are only possible from the terminal blocks of the LON-Bus devices. Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products...
I-Bus devices. Function / I-Bus address Programming switch S3 S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 Module out of commission (not used) I-Bus device number ”S3-1...6” are set to ”off” at the factory Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus modules Plug-in terminals blue Supply blue to other I-Bus modules I-Bus modules green Double flat cable header from previous I-Bus modules Data communication I-Bus modules to other I-Bus modules Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Communication and supply via flat cable Card format 100mm x 160mm 12.2 Application Two application possibilities are provided: a) Installation in the control unit FC700A b) Installation at the rear of the control terminal FT700A Application a) 2 RS232 interfaces from B3Q700 (FC700A) –...
(ground 1) 0V1 (transmit) TXD2 (receive) RXD2 RTS2 Modem CTS2 RS232-2 extended TCLK2 functions (SWE700A) RCLK2 (ground 2) 0V2 Depending on type of modem the signals 'RTS/CTS' must not be wired Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
E3I020 RS232 module 12.6 Important components Installation in control unit FC700A Terminal block (supplied with Z1I030) Flat cable F20A140 for applica tion in control unit to B3Q700 E3I020 connector "ST2" Connector "ST1": RS232 (2 x HCMOS level) Connector "ST2": for the insertion of a plug-in terminal block Plug-in terminals for "ST2"...
Station type FG700A Download of FG configuration data necessary Processing capacity see document 007836 Automatic data transfer of all FC700A to FG700A in the start-up phase – For FG700A → CKQ007.60 (EPROM Set 2x 512Kx8Bit) – Install in the fire detection control unit FC700A –...
Wiring principle Fire detection control unit C-Bus 24V/5VDC E3H020 I-BUS FC700A ISO 1745 Protocol RS232 Lines Control modules Detectors 13.5 Supply wiring principle C-Bus E3H020 24V/5VDC Supply I-Bus I-Bus Data communication Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Jumper must always be inserted (inserted at factory) 24V OUT 1) Configuration as In-/or output see also jumpers X15, X16, X17, X18, Y15, Y16, Y17, Y18 table in chapter Important components Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Page 56
I-Bus modules I-Bus modules green Double flat cable header from previous I-Bus modules Data communication I-Bus modules to other I-Bus modules Flat cable header unused Interface asynchronous TTL Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
- mounted on module chassis - for the connection of the prefabricated cable to connection level, or - for direct connection of the periphery E3L020 Card chassis - mounted on module chassis Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus devices. Function / I-Bus address Programming switch S3 S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 Module out of commission (unused) I-Bus user number ”S3-1...6” are set to ”off” at the factory Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus modules Plug-in terminals blue Supply for blue I-Bus modules to other I-Bus modules green Double flat cable header from previous I-Bus modules Data communication I-Bus modules to other I-Bus modules Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
10Ω per wire* Line resistance for SST max. 10Ω per wire* Control output load max. 40mA with EMI protection Quiescent current at 24V 18mA (normal operating mode) * For details see page 63 Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Module supply remove depending on 3rd party Fuse with high breaking capacity (sand-filled) extinguishing system Plug-in terminals "K1": Programming switch "S3": Supply for "I-Bus" modules Setting "I-Bus address" (see chapter Programming switch) Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus modules blue blue Supply for to other I-Bus modules I-Bus modules green Double flat cable header from previous I-Bus modules Data communication I-Bus modules to other I-Bus modules Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
- mounted on module chassis - for the connection of the prefabricated cable to connection level, or - for direct connection of the periphery E3G050 Card chassis - mounted on module chassis Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus devices. Function / I-Bus address Programming switch S3 S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 Module out of commission (unused) I-Bus user number ”S3-1...6” are set to ”off” at the factory Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus modules Plug-in terminals blue Supply for blue I-Bus modules to other I-Bus modules green Double flat cable header from previous I-Bus modules Data communication I-Bus modules to other I-Bus modules Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
- mounted on module chassis - for the connection of the prefabricated cable to connection level, or - for direct connection of the periphery E3G060 Card chassis - mounted on module chassis Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
I-Bus devices. Function / I-Bus address Programming switch S3 S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 Module out of commission (unused) I-Bus user number ”S3-1...6” are set to ”off” at the factory Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Switch ”S7” defines global horn mode for all horn outputs. Invert this mode (constant / intermitted) individually for each horn output by connecting common (X1-1) with corresponding control input (X1-15.. 20). Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
24V / 12A Double flat cable header from previous I-Bus modules Data communication I-Bus modules to other I-Bus modules 1) The indicated polarity at the terminals 2...14 applies to the active state Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
- mounted on module chassis - for the connection of the prefabricated cable to connection level, or - for direct connection of the periphery E3G070 Card chassis - mounted on module chassis Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
”S3-1...6” are set to ”off” at the factory The I-Bus address setting is given as default by the tool (SWE700A) as address 15, therefore the programming switch 'S3' of the E3G070 must be set accordingly. Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products...
I-Bus module E3M111 1) The indicated polarity at the terminals 5...8 applies to the active state 2) The output X1-9,10 is always monitored 3) Terminate not used horn lines with a 4,75kΩ resistor Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
External voltage side (contact) Control unit voltage side (coil) 19.1 Connections Z3B171 e.g. e.g. 900Ω E3G070/Q3 air conditioning control 10A 250VAC Terminal layout Relay Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Principle of the insertable inscription strips see page 77 20.1 Overview Control terminal for the fire control unit FC700A Becomes at the same time used as ’main-CPU’ For full system operating Can be used for single or multi AREA operating...
’FC700A’ B3Q700 FT700A-1 -> CTY00760 international 1) FC700A-1 -> CIY00760 international 1) Default programming at factory by using it as spare part for FC700A, the file CIY00760 must be downloaded. The Flash program files are available from the Hotline. 20.4...
X31 + X32 + X33 + X34 ”FC” + autonomous supply (Output) Y31 + Y32 + Y33 + Y34 If the control terminal B3Q700 is used as replacement for FC700A -> change the 0Ω−Resistors from pos. X31…..X34 to pos. Y31….Y34 Siemens Building Technologies 007831_a_en_--.doc...
C-Bus participants are connected 2) Configuration as in-/or output see jumpers X31, X32, X33, X34, Y31, Y32, Y33, Y34 on table in chapter important components Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products...
”Lamp test” is contained in the menu function of control terminal B3Q700 21.2 Application Installation The parallel indicator panel B3R051 fits in the following housings: Control unit housing FC700A – Plastic housing ”small” H23G220 (1x B3R051) – Housing H28G200 with cover H28T110 for 1x B3R051 and B3Q700 –...
Z3I350 24V supply line Note: max. 24 units B3R051 or K3R072 (also mixed) possible with max. 8 different addresses – remove resistor array (see page 83) except on one unit – Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
B3Q700, ST4 Data bus (via flat cable) from K3I050, ST2 Flat cable header Data bus (via flat cable) to other B3R051/K3R072 Note: Remove eventually resistor array. Must be assembled for device! Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
49+50 for 'LED operation' LED 25..48 K3R072 wires 49+50 unused K3R072 These in-/outputs can be in Key 'Switch-off buzzer' parallel with other K3R072 Key 'Lamp test' if located in same cabinet Buzzer Z3I520 Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Programming switch S1 S1-1 S1-2 S1-3 S1-4 Test procedure In this setting all outputs are activated alternating between even and uneven numbers. Equipment address ”S1-1...4” are set to ”off” at the factory Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
K3G060 23.3 Wiring principle external potential external potential Relay outputs Data bus (V+/V-) Relay outputs (V+/V-) K3R072 K3G060 K3G060 ST11 ST12 0,25m 0,25m Data bus relay Data bus relay activation activation Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Jumper open: are set to NEUTRAL at the factory Terminal block "K2": Relay output channels 1..24 Connector 50-pin "ST1" with flat cable (length 0,25m) Possibility to connect V+ / V- potential Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
X1..X24 are set to NEUTRAL at the factory max. 30V / 1A Rel.24 Channel 24 Terminals external potential (switchable via jumper X1..X24) Flat cable header ST1 from K3R072 'ST11' or 'ST12' Energizing relays 1..24 Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
-remains active until input 'buzzer OFF' is activated or the cause for a) or b) no longer exists Input 'lamp test' -activates all LED outputs within the K3R072, B3R051 for apprx. 2 sec. Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products...
Maximum 32 LON-Bus devices. Function / LON-Bus address Programming switch S3 S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 Module out of commission (not used) LON-Bus device number ”S3-1...6” are set to ”off” at the factory Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
* all relay activated incl. service LED 25.4 Wiring principle max. length of LON-Bus 1000m LON-Bus E3I040 B3Q590/ K3I050 B3Q580 K3I110 Data bus 16 programmable control outputs max. 30V /1A 16 programmable monitored control inputs Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
= not monitored (factory setting) left = monitored Key 'S2': Service press 2 seconds to initiate lamp test (LED and relay), each relay and/or LED (H1...H16) is activated one after the other Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Programming switch ’S3’ Function / LON-Bus address Programming switch S3 S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 Module out of commission (not used) LON-Bus device number ”S3-1...6” are set to ”off” at the factory Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
4k75 control input 15 programmable monitored control input 16 from E3I040 or from previous LON device Plug-in terminals K1 not used Supply 9...45VDC 24V supply Earth LON-Bus to other LON device Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Maximum 32 LON-Bus devices. Function / LON-Bus address Programming switch S3 S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 Module out of commission (not used) LON-Bus device number ”S3-1...6” are set to ”off” at the factory Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
1 ----> <-tx1->xxx Special function: <--------- customer text 2 ---------> – different display mode nn%<--------- customer text 1 ---------> A = on alarm <--------- customer text 2 ---------> B = on fault Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
31.12.2000 Time format: 23:59 Time format: 23.59 National characters: ƒ ‰ ÷ ˆ ‹ ¸ ≈ Â È § \ National characters: ∅ ¯ ∆ Ê ≈ Â \ ° ~ Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Page 105
Date format: 31.12.2000 Time format: 23:59 Time format: 23:59 National characters: È Ì ˚ ¸ ı Û ˆ \ ~ Ë Ï Ú ∅ ¯ š ý National characters: \ ° Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
Page 106
Date format: 31-12-2000 Date format: 31-12-2000 Time format: 23:59 Time format: 23:59 National characters: £ \ ~ National characters: ¡ ∆ Ð … Õ ” ÷ ⁄ Ý Þ \ ° Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...
LON device Terminal block Input programmable LED 3 Use ground potential to control inputs (if input is connected to ground, LED is active) Input programmable LED 2 Input programmable LED 1 Siemens Building Technologies 007831_a_en_--.doc Fire & Security Products 03.2004...