ABB REC650 Product Manual
Hide thumbs Also See for REC650:

Advertisement

®
Relion
650 series
Bay control REC650 ANSI
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB REC650

  • Page 1 ® Relion 650 series Bay control REC650 ANSI Product Guide...
  • Page 2: Table Of Contents

    11. Metering.................30 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2012 ABB.
  • Page 3: Series Overview

    The packages are configured and ready for direct 2. Application use. Analog and control circuits have been pre- REC650 is used for the control, protection and defined. Other signals need to be applied as monitoring of different types of bays in power required for each application.
  • Page 4 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 132 kV Bus REC650-A01A – Single Busbar Single breaker 10AI (4I+1I+5U) Control Control Control 132kV/110V S CILO S CSWI S XSWI Meter. V MMXU Control Control Control 189G S CILO...
  • Page 5 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 REC650-A02A – Double Busbar Single breaker 10AI (4I+1I+5U) 132 kV Bus Control Control Control S CILO S CSWI S XSWI Control Control Control 132kV/ S CILO S CSWI S XSWI...
  • Page 6 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1189G 2189G REC650-A07A – Bus Coupler single breaker 10AI (4I+6U) 132 kV Bus Control Control Control S CILO S CSWI S XSWI Control Control Control 132kV/ S CILO S CSWI...
  • Page 7: Available Functions

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 3. Available functions...
  • Page 8 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Control and monitoring functions IEC 61850/Function ANSI Function description block name Control SESRSYN Synchrocheck, energizing check, and 0–1 synchronizing SMBRREC Autorecloser for 3–phase operation 0–1 APC8 Apparatus control for single bay, max 8 app.
  • Page 9 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 IEC 61850/Function ANSI Function description block name LOCREMCTRL LHMI control of Permitted Source To Operate (PSTO) SLGGIO Logic Rotating Switch for function selection and LHMI presentation VSGGIO Selector mini switch extension...
  • Page 10 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 IEC 61850/Function ANSI Function description block name Configurable logic blocks, exclusive OR gate LOOPDELAY Configurable logic blocks, loop delay TIMERSET Configurable logic blocks, timer function block Configurable logic blocks, AND gate...
  • Page 11 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 IEC 61850/Function ANSI Function description block name INDEXTSPQT Configurable logic Q/T, single point indication logic signal gate extracting value with quality and time Configurable logic blocks Q/T 0–1 FXDSIGN...
  • Page 12 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 IEC 61850/Function ANSI Function description block name CNTGGIO Event counter DRPRDRE Disturbance report AxRADR Analog input signals BxRBDR Binary input signals SPGGIO IEC 61850 generic communication I/O functions SP16GGIO...
  • Page 13 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 IEC 61850/Function ANSI Function description block name Metering PCGGIO Pulse counter logic ETPMMTR Function for energy calculation and demand handling...
  • Page 14 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Back-up protection functions IEC 61850/ ANSI Function description Function block name Current protection PHPIOC Instantaneous phase overcurrent 0–1 protection, 3–phase output OC4PTOC Four step phase overcurrent protection, 3– 0–1...
  • Page 15 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 IEC 61850/ ANSI Function description Function block name Frequency protection SAPTUF Underfrequency function 0–2 SAPTOF Overfrequency function 0–2 SAPFRC Rate-of-change frequency protection 0–2...
  • Page 16 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Communication IEC 61850/Function ANSI Function description block name Station communication IEC61850-8-1 IEC 61850 communication protocol DNPGEN DNP3.0 for TCP/IP communication protocol RS485DNP DNP3.0 for EIA-485 communication protocol CH1TCP DNP3.0 for TCP/IP communication...
  • Page 17 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 IEC 61850/Function ANSI Function description block name OPTICAL103 IEC60870-5-103 Optical serial communication RS485103 IEC60870-5-103 serial communication for RS485 GOOSEINTLKRCV Horizontal communication via GOOSE for interlocking GOOSEBINRCV GOOSE binary receive...
  • Page 18 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Basic IED functions IEC 61850/Function Function description block name Basic functions included in all products INTERRSIG Self supervision with internal event list SELFSUPEVLST Self supervision with internal event list...
  • Page 19: Control

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 other functions such as interlocking, synchronism 4. Control check, operator place selection and external or Synchrocheck, energizing check, and internal blockings. synchronizing SESRSYN (25) The Synchronizing function allows closing of...
  • Page 20 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Local remote LOCREM /Local remote control LOCREMCTRL The signals from the local HMI or from an external local/remote switch are applied via the function blocks LOCREM and LOCREMCTRL to the Bay control (QCBAY) function block.
  • Page 21: Current Protection

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 VSGGIO can be controlled from the menu or from a The directional function is voltage polarized with symbol on the single line diagram (SLD) on the local memory. The function can be set to be directional HMI.
  • Page 22 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Second harmonic blocking restraint level can be set protection one time constant, Fahrenheit LFPTTR for the function and can be used to block each step (26) or Celsius LCPTTR.
  • Page 23: Voltage Protection

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 overcurrent function is released from a normally Negative sequence based overcurrent function open, 89b auxiliary contact on the line disconnector. DNSPTOC (46) Negative sequence based overcurrent function Pole discordance protection CCRPLD (52PD)
  • Page 24: Frequency Protection

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 voltage. When triggered, the function will cause an Overfrequency protection SAPTOF (81) alarm, switch in reactors, or switch out capacitor Overfrequency protection function SAPTOF (81) is banks. applicable in all situations, where reliable detection...
  • Page 25: Logic

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 A detection of a difference indicates a fault in the in a control circuit is detected by using a dedicated circuit and is used as alarm or to block protection output contact that contains the monitoring functions expected to give unwanted tripping.
  • Page 26 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 • GATE function block is used for whether or not a • PULSETIMERQT function block can be used, for signal should be able to pass from the input to example, for pulse extensions or limiting of the output.
  • Page 27: Monitoring

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 state part is toggled. The function also IEC61850 generic communication 1/O function 16 propagates timestamp and quality of input signals. inputs IEC 61850 generic communication I/O functions 16 • INDEXTSPQT extracts individual signals from a inputs (SP16GGIO) function is used to send up to group signal input.
  • Page 28 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 The Disturbance report function is characterized by Event recorder DRPRDRE great flexibility regarding configuration, initiating Quick, complete and reliable information about conditions, recording times, and large storage disturbances in the primary and/or in the secondary capacity.
  • Page 29 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 to the Disturbance report function (maximum 40 the high accuracy achieved by compensating for analog and 96 binary signals). The binary signals load current and for the mutual zero-sequence available are the same as for the event recorder effect on double circuit lines.
  • Page 30: Metering

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 12. Human Machine interface Circuit breaker monitoring SSCBR The circuit breaker condition monitoring function Local HMI SSCBR is used to monitor different parameters of the circuit breaker. The breaker requires maintenance when the number of operations has reached a predefined value.
  • Page 31: Basic Ied Functions

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 13. Basic IED functions There are two ways of entering the test mode: Self supervision with internal event list • By configuration, activating an input signal of The Self supervision with internal event list...
  • Page 32 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 61850-8-1. IEC 61850-8-1 protocol allows second. If the quota is exceeded the event channel intelligent electrical devices (IEDs) from different transmission is blocked until the event changes is vendors to exchange information and simplifies below the quota, no event is lost.
  • Page 33: Hardware Description

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 terminology, a primary station is a master and a selection for optical serial (OPTICALPROT) and secondary station is a slave. The communication is Operation selection for RS485 (RS485PROT) are based on a point-to-point principle.
  • Page 34 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Rack mounting a single 3U IED ANSI11000248 V1 EN Figure 7. Rack mounted 3U IED A 8.82 inches (224 mm) + 0.47 inches (12 mm) with ring-lug connectors B 1 inches (22.5 mm) C 19 inches (482 mm) D 5.20 inches, 3U (132 mm)
  • Page 35: Connection Diagrams Customized

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 16. Connection diagrams Customized Connection diagrams for 650 series ANSI12000601 V1 EN Figure 8. Designation for 3U, 1/1x19" casing with 1 TRM ANSI12000602 V1 EN Figure 9. Designation for 3U, 1/1x19" casing with 1 TRM and 1 AIM...
  • Page 36 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 ANSI12000603 V1 EN Figure 10. Communication module (COM)
  • Page 37 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 ANSI12000604 V1 EN Figure 11. Power supply module (PSM) 48-125V DC ANSI12000605 V1 EN Figure 12. Power supply module (PSM) 110-250V DC, 100–240V AC...
  • Page 38 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 ANSI12000606 V1 EN Figure 13. Transformer module (TRM) ANSI12000607 V1 EN Figure 14. Analog input (AIM)
  • Page 39 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 ANSI12000608 V1 EN Figure 15. Binary input/output (BIO) option...
  • Page 40: Connection Diagrams Configured

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 17. Connection diagrams Configured 1MRK006502-CC-3-PG-ANSI V1 EN Figure 16. Designation for 3U, 1/1x19" casing with 1 TRM (A01A/A02A/A07A)
  • Page 41 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Connection diagrams for REC650 A01A 1MRK006502-DC-PG-1.2-ANSI V1 EN Figure 17. Communication module (COM)
  • Page 42 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-DC-5-PG-1.2-ANSI V1 EN Figure 18. Power supply module (PSM) 48-125V DC...
  • Page 43 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-DC-6-PG-1.2-ANSI V1 EN Figure 19. Power supply module (PSM), 110-250V DC, 100–240V AC...
  • Page 44 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-DC-7-PG-1.2-ANSI V1 EN Figure 20. Transformer module (TRM)
  • Page 45 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-DC-8-PG-1.2-ANSI V1 EN Figure 21. Binary input/output (BIO) option...
  • Page 46 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-DC-9-PG-1.2-ANSI V1 EN Figure 22. Binary input/output (BIO) option...
  • Page 47 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-DC-10-PG-1.2-ANSI V1 EN Figure 23. Binary input/output (BIO) option...
  • Page 48 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Connection diagrams for REC650 A02A 1MRK006502-CC-PG-1.2-ANSI V1 EN Figure 24. Communication module (COM)
  • Page 49 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-CC-5-PG-1.2-ANSI V1 EN Figure 25. Power supply module (PSM) 48-125V DC...
  • Page 50 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-CC-6-PG-1.2-ANSI V1 EN Figure 26. Power supply module (PSM), 110-250V DC, 100–240V AC...
  • Page 51 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-CC-7-PG-1.2-ANSI V1 EN Figure 27. Transformer module (TRM)
  • Page 52 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-CC-8-PG-1.2-ANSI V1 EN Figure 28. Binary input/output (BIO) option...
  • Page 53 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-CC-9-PG-1.2-ANSI V1 EN Figure 29. Binary input/output (BIO) option...
  • Page 54 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-CC-10-PG-1.2-ANSI V1 EN Figure 30. Binary input/output (BIO) option...
  • Page 55 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-CC-11-PG-1.2-ANSI V1 EN Figure 31. Binary input/output (BIO) option...
  • Page 56 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Connection diagrams for REC650 A07A 1MRK006502-BC-4-PG-1.2-ANSI V1 EN Figure 32. Communication module (COM)
  • Page 57 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-BC-5-PG-1.2-ANSI V1 EN Figure 33. Power supply module (PSM) 48-125V DC...
  • Page 58 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-BC-6-PG-1.2-ANSI V1 EN Figure 34. Power supply module (PSM), 110-250V DC, 100–240V AC...
  • Page 59 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-BC-7-PG-1.2-ANSI V1 EN Figure 35. Transformer module (TRM)
  • Page 60 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-BC-8-PG-1.2-ANSI V1 EN Figure 36. Binary input/output (BIO) option...
  • Page 61 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-BC-9-PG-1.2-ANSI V1 EN Figure 37. Binary input/output (BIO) option...
  • Page 62 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-BC-10-PG-1.2-ANSI V1 EN Figure 38. Binary input/output (BIO) option...
  • Page 63 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 1MRK006502-BC-11-PG-1.2-ANSI V1 EN Figure 39. Binary input/output (BIO) option...
  • Page 64: Technical Data

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 18. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the...
  • Page 65 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Auxiliary AC and DC voltage Table 3. Power supply Description 600PSM02 600PSM03 48, 60, 110, 125 V DC 100, 110, 120, 220, 240 V AC, 50 and 60 Hz...
  • Page 66 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 6. Power output relays without TCM function Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s...
  • Page 67 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 10. X8/IRIG-B and EIA-485 interface Type Protocol Cable Screw terminal, pin row IRIG-B Shielded twisted pair cable header Recommended: CAT 5, Belden RS-485 (9841- 9844) or Alpha Wire (Alpha 6222-6230)
  • Page 68 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 14. Optical serial port (X9) Wave length Fibre type Connector Permitted path attenuation 820 nm MM 62,5/125 µm glass 6.8 dB (approx. 1700m length with 4 db / km fibre...
  • Page 69 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 18. Environmental tests Description Type test value Reference Cold tests operation 96 h at -25ºC IEC 60068-2-1/ANSI C37.90-2005 16 h at -40ºC (chapter 4) storage 96 h at -40ºC...
  • Page 70 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Type tests according to standards Table 19. Electromagnetic compatibility tests Description Type test value Reference 100 kHz and 1 MHz burst disturbance IEC 61000-4-18, level 3 test IEC 60255-22-1 ANSI C37.90.1-2002...
  • Page 71 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 19. Electromagnetic compatibility tests, continued Description Type test value Reference Voltage dips and short interruptionsc Dips: IEC 60255-11 on DC power supply 40%/200 ms IEC 61000-4-11 70%/500 ms...
  • Page 72 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 20. Insulation tests Description Type test value Reference Dielectric tests: IEC 60255-5 ANSI C37.90-2005 • Test voltage 2 kV, 50 Hz, 1 min 1 kV, 50 Hz, 1 min, communication...
  • Page 73 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 EMC compliance Table 23. EMC compliance Description Reference EMC directive 2004/108/EC Standard EN 50263 (2000) EN 60255-26 (2007) Current protection Table 24. Instantaneous phase overcurrent protection, 3-phase output PHPIOC (50)
  • Page 74 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 25. Four step phase overcurrent protection, 3-phase output OC4PTOC (51/67) Function Setting range Accuracy lBase Operate current (5-2500)% of ± 1.0% of I at I ≤ I ± 1.0% of I at I > I Reset ratio >...
  • Page 75 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 26. Instantaneous residual overcurrent protection EFPIOC (50N) Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >...
  • Page 76 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 27. Four step residual overcurrent protection EF4PTOC (51N/67N) Function Range or value Accuracy lBase Operate current (1-2500)% of ± 1.0% of I at I < I ± 1.0% of I at I > I Reset ratio >...
  • Page 77 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 28. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) Function Range or value Accuracy lBase Operate level for 3I ·cosj (0.25-200.00)% of ± 1.0% of I at I £ I directional residual ±...
  • Page 78 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 28. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) , continued Function Range or value Accuracy Reset time, non-directional 90 ms typically at 1.2 to 0.5 x I...
  • Page 79 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 30. Breaker failure protection, 3-phase activation and output CCRBRF (50BF) Function Range or value Accuracy lBase Operate phase current (5-200)% of ± 1.0% of I at I £ I ±...
  • Page 80 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 33. Broken conductor check BRCPTOC (46) Function Range or value Accuracy IBase Minimum phase current for operation (5–100)% of ± 1.0% of I Unbalance current operation (50-90)% of maximum current ±...
  • Page 81 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 35. Negative sequence based overcurrent function DNSPTOC (46) Function Range or value Accuracy IBase Operate current (2.0 - 5000.0) % of ± 1.0% of I at I <I ±...
  • Page 82 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Voltage protection Table 36. Two step undervoltage protection UV2PTUV (27) Function Range or value Accuracy Operate voltage, low and high step (1–100)% of VBase ± 0.5% of V Reset ratio <105%...
  • Page 83 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 38. Two step residual overvoltage protection ROV2PTOV (59N) Function Range or value Accuracy VBase Operate voltage, step 1 (1-200)% of ± 0.5% of V at V < V ±...
  • Page 84 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Frequency protection Table 40. Under frequency protection SAPTUF (81) Function Range or value Accuracy Operate value, pickup function (35.00-75.00) Hz ± 2.0 mHz Operate value, restore frequency (45 - 65) Hz ±...
  • Page 85 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Secondary system supervision Table 43. Current circuit supervision CCSRDIF (87) Function Range or value Accuracy Operate current (5-200)% of I ± 10.0% of I at I £ I ± 10.0% of I at I > I...
  • Page 86 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Control Table 46. Synchronizing, synchronism check and energizing check SESRSYN (25) Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage ratio, V 0.500 - 2.000...
  • Page 87 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 47. Autorecloser for 3-phase operation SMBRREC (79) Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 3Ph (0.000-60.000) s ±...
  • Page 88 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 49. Configurable logic blocks Logic block Quantity with cycle time Range or value Accuracy 5 ms 20 ms 100 ms INVERTER SRMEMORY RSMEMORY GATE PULSETIMER (0.000–90000.000) s ± 0.5% ± 25 ms for...
  • Page 89 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Monitoring Table 51. Technical datacovering measurement functions:CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU Function Range or value Accuracy Voltage (0.1-1.5) ×V ± 0.5% of V at V£V ± 0.5% of V at V > V Connected current (0.2-4.0) ×...
  • Page 90 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 53. Disturbance report DRPRDRE Function Range or value Accuracy Current recording ± 1,0% of I at I ≤ I ± 1,0% of I at I > Ir Voltage recording ±...
  • Page 91 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 55. Event list DRPRDRE Function Value Buffer capacity Maximum number of events in the list 1000 Resolution 1 ms Accuracy Depending on time synchronizing Table 56. Indications DRPRDRE...
  • Page 92 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 60. Station battery supervision SPVNZBAT Function Range or value Accuracy Lower limit for the battery terminal (60-140) % of Vbat ± 1.0% of set battery voltage voltage Reset ratio, lower limit <105 %...
  • Page 93 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Metering Table 64. Pulse counter PCGGIO Function Setting range Accuracy Cycle time for report of counter (1–3600) s value Table 65. Function for energy calculation and demand handling ETPMMTR...
  • Page 94 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Station communication Table 66. Communication protocol Function Value Protocol TCP/IP Ethernet Communication speed for the IEDs 100 Mbit/s Protocol IEC 61850–8–1 Communication speed for the IEDs 100BASE-FX Protocol DNP3.0/TCP...
  • Page 95 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Inverse time characteristics Table 70. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç...
  • Page 96 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 72. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic td = (0.05-999) in steps of 0.01 × 0.236 0.339 EQUATION1656 V1 EN...
  • Page 97 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Table 74. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 ±5% +60 ms æ ö VPickup V ç...
  • Page 98: Ordering For Customized Ied

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 19. Ordering for Customized IED Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections.
  • Page 99 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Current protection Instantaneous phase overcurrent protection, 3–phase output Qty: 1MRK 004 908-AA (PHPIOC, 50) Four step phase overcurrent protection, 3–phase output Qty: 1MRK 004 908-BB (OC4PTOC, 51/67) Instantaneous residual overcurrent protection (EFPIOC, 50N)
  • Page 100 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Secondary system supervision Current circuit supervision (CCSRDIF, 87) Qty: 1MRK 004 914-AA Fuse failure supervision (SDDRFUF) Qty: 1MRK 004 914-BA Control Synchrocheck, energizing check and synchronizing Qty: 1MRK 004 917-AC (SESRSYN, 25) Autorecloser for 3–phase operation (SMBRREC, 79)
  • Page 101 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Analog system Rule: One Transformer input module must be ordered Transformer module (TRM) 6I+4U, 1/5A,100/220V Qty: 1KHL178083R0001 Transformer module (TRM) 8I+2U, 1/5A, 100/220V Qty: 1KHL178083R0013 Transformer module (TRM) 4I, 1/5A+1I, 0.1/0.5A+5U, 100/220V...
  • Page 102: Ordering For Configured Ied

    To obtain the complete ordering code, please combine code from the tables, as given in the example below. Exemple code: REC650*1.2-A01AX00-X00-B1A5-B-A-SA-AB1-RA3-AAAA-E. Using the code of each position #1-11 specified as REC650*1-2 2-3-4 4-5-6-7 7-8 8-9 9-10 10 10 10-11 - 10...
  • Page 103 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Casing Notes and Rules Rack casing, 3U 1/1 x 19" Selection for position #5. Mounting details with IP40 of protection from the front Notes and Rules No mounting kit included Rack mounting kit for 3U 1/1 x 19"...
  • Page 104 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Binary input/output module Notes and Rules Slot position (rear view) Available slots in 1/1 case No board in slot Binary input/output module 9 BI, 3 NO Trip, 5 p6 optional for A01A...
  • Page 105: Ordering For Accessories

    Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 21. Ordering for Accessories Configuration and monitoring tools Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA...
  • Page 106 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Rule: Specify the number of printed manuals requested Operation manual ANSI Quantity: 1MRK 500 095-UUS Technical manual ANSI Quantity: 1MRK 511 263-UUS Commissioning manual ANSI Quantity: 1MRK 511 264-UUS...
  • Page 107 Bay control REC650 ANSI 1MRK 511 265-BUS B Product version: 1.2 Related documents Documents related to REC650 Identity number Application manual 1MRK 511 262-UUS Technical manual 1MRK 511 263-UUS Commissioning manual 1MRK 511 264-UUS Product Guide 1MRK 511 265-BUS Type test certificate...
  • Page 109 ABB Inc. 3450 Harvester Road Burlington, ON L7N 3W5, Canada Phone Toll Free: 1-800-HELP-365, menu option #8 ABB Mexico S.A. de C.V. Paseo de las Americas No. 31 Lomas Verdes 3a secc. 53125, Naucalpan, Estado De Mexico, MEXICO Phone (+1) 440-585-7804, menu...

Table of Contents