4.3 FACEPLATE INTERFACE
4 HUMAN INTERFACES
flash message will appear upon activation of the ten minute timeout or any other time a user attempts any
FOR 10 MIN!
change to the defined tier during the ten minute timeout. The
FlexLogic™ operand will be set to
LOCAL ACCESS DENIED
"Off" after the expiration of the ten-minute timeout.
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the
FlexLogic™ operand will be set to "On" and
REMOTE ACCESS DENIED
the C30 will not allow Settings or Command access via the any external communications interface for the next ten minutes.
The
FlexLogic™ operand will be set to "Off" after the expiration of the ten-minute timeout.
REMOTE ACCESS DENIED
4
4-28
C30 Controller System
GE Multilin