Object List - Toshiba Black Pear Installation And User Manual

Bms interface for toshiba air-conditioning
Table of Contents

Advertisement

9.3 Object List

Object
On/Off (Setup)
On/Off (State)
Error Code
Operation Mode (Setup)
Operation Mode (State)
Fan Speed (Setup)
Fan Speed (State)
Room Temperature
Setpoint Temperature
(Setup)
Setpoint Temperature
(State)
Local Inhibit (Setup)
Local Inhibit (State)
Object Type
Binary Output
Binary Input
Analog Input
Multi-State Output
Multi-State Input
Multi-State Output
Multi-State Input
Analog Input
Analog Output
Analog Input
Binary Output
Binary Input
26
Instance
'Present Value'
No.
Settings
1xxx01
Inactive:Off
Active:On
1xxx02
Inactive:Off
Active:On
1xxx03
4 digit error code where
8000= 'No Error'
6999= 'Unit Not Present'
1xxx04
01: Fan
02: Cool
03: Heat
04: Dry
05: Auto
06: N/A
07: Auto Cool
08: Auto Heat
09: Heat Exchange
10: VN-Auto
11: VN-Bypass
1xxx05
01: Fan
02: Cool
03: Heat
04: Dry
05: Auto
06: N/A
07: Auto Cool
08: Auto Heat
09: Heat Exchange
10: VN-Auto
11: VN-Bypass
1xxx06
01: Low
02: Medium
03: High
04: Auto
1xxx07
01: Low
02: Medium
03: High
04: Auto
1xxx08
o
1xxx09
18.0
C to 29.0
o
1xxx10
18.0
C to 29.0
1xxx11
Inactive:Off
Active:Inhibit
1xxx12
Inactive:Off
Active:Inhibited
Notes
See
Appendix D
Not
settable
VN units
only
VN units
only
o
C
o
C

Advertisement

Table of Contents
loading