Electrolux Premium Quick Reference Manual page 22

Thermoregulator management controller
Table of Contents

Advertisement

dt2: end defrost temperature set point, auxiliary evaporator
dt2 acts in the same way as parameter dt1 described above, but referring to the auxiliary evaporator.
Note for dt1 and dt2:
in the defrost by temperature, the parameter establishes the threshold for activating or deactivating the
corresponding defrost relay.
Default: dt2 =4°C.
dP1: Maximum evaporator defrost duration
Determines the maximum defrost duration on the evaporator in minutes (or seconds, see parameter dC) if defrost by temperature is
selected. If timed defrost has been selected, this is the actual duration of the defrost. Default: dP1=30 minutes.
dP2: Maximum defrost duration, auxiliary evaporator
As for parameter dP1 described above, but refers to the auxiliary evaporator.
Default: dP2=30 minutes.
d3: Defrost start delay
This parameter determines the time that must elapse, when the defrost is activated, between the
stopping of the compressor (electric heater defrost) or the starting of the compressor (hot gas defrost), and the activation of the
defrost relays on the main and auxiliary evaporators.
The delay d3 is useful, in the hot gas defrost, to ensure a suffi cient quantity of hot gas for the defrost before the activation of the cycle
reversing valve, in very special applications (see paragraph "Description of software functions"). Default: d3=0 minutes.
d4: Defrost when the instrument is switched on
Activates a defrost when the instrument is switched on.
Warning:
this request has priority over the activation of the compressor and the continuous cycle.
The possible values are:
d4=0, no defrost is performed when the instrument is switched on;
d4=1, a defrost is performed when the instrument is switched on.
Starting a defrost when the instrument is switched on may be useful in special situations.
Example:
frequent power drops occur in the system, which cause the internal clock to be reset. This clock calculates the interval
between two defrosting operations, restarting from zero. If the frequency of the power failure were, in an extreme case, greater
than the defrost frequency (e.g. a power failure every hour, against a defrost every 10 hours) the controller would never perform a
defrost. In a situation of this type, it is preferable to enable defrost on start-up, above all if the defrost is controlled by temperature
(probe on the evaporator), therefore avoiding unnecessary defrosts or at least reducing the running times. In the case of systems
with a large number of units, if selecting defrosts at start-up, after a power failure all the units will start defrosting, thus causing a
voltage overload. To overcome this, the parameter d5 can be used. It adds a delay before the defrost, and this delay must obviously
be diff erent for each unit.
Default: d4=0 the instrument does not perform a defrost on start-up.
Available on all models except for IR33M.
d5: Defrost delay when the instrument is switched on or from multifunction input
The time that must elapse between start-up of the controller and the start of the defrost.
• if the digital input is used to enable the defrost (see parameter A4, A5, A9=3) or to start a defrost from external contact (see
parameter A4, A5, A9=4), the parameter d5 refers to the delay between enabling of the defrost or request to enable, and the
eff ective start.
• the defrost digital input (see parameter A4, A5, A9) can be usefully employed to perform defrosts in real time, connecting a timer
to the input. The defrost will be activated when the timer contact closes.
• If several units are connected to the same timer, parameter d5 should be used to delay the various defrosts, thus avoiding power
overloads.
In addition, to avoid unwanted defrosts started by the clock inside the instrument, set parameter dI=0 (manual defrosts only,
started from the keypad, by the RTC, by the calculation of the compressor running time or by the multifunction contact).
Important warning:
when connecting a series of units to the same timer, the best solution is to insulate all the contacts galvanically,
fi tting intermediate relays for each contact.
Default: d5=0 => no delayed defrost when switching the instrument on or following the activation of the multifunction input.
From ser. no.:
Page:22
Ed.1" 08-2014
560001 EG
Doc. No.:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Standard

Table of Contents