Truck - ABB AMVAC Installation And Operation Manual

Medium voltage vacuum circuit breakers
Hide thumbs Also See for AMVAC:
Table of Contents

Advertisement

T
:
RUCK
The truck requires visual inspection of hardware, lubrication and operations during routine maintenance.
With the breaker outside the cell, verify all visible hardware tightness, including handles (9) and wheels (7). Wheels
should rotate freely by hand movement. Replace or tighten any missing or loose hardware.
With the breaker outside the cell, rotate the racking screw as though racking the breaker to the connect position. This
process will expose surfaces inside the truck that need to be inspected and lubricated. Lubricate the Racking Screw on-
ly. Inspect the Racking Screw (2), Position Release Shaft (3), breaker locking tabs (8), Secondary Locking Tab (1) for
any damage. Return truck to disconnect position. As a precaution, do not operate the breaker outside the cell unless
the truck is in the full disconnect position.
7
7
8
9
1
2
3
4
5
6
7
20
MAINTENANCE
2
4
13
5
Figure 3: (Truck shown with breaker removed)
Secondary Locking Tab
Racking Screw
Position Release Shaft
Grounding Connection
Racking
Pin
Monitor/Close
Blocking Switch
Position Release Lever
Wheels
1VAL050601-MB Rev C
3
11
10
8
Cell Locking Tabs
9
Insertion/Removal Handles
10
Collar
11
Racking Lock For Tag-Out
12
N/A
13
Racking Pin
1
7
6
9
7
8

Advertisement

Table of Contents
loading

Table of Contents