Appendix; List Of Important Alarms And Faults; A.1 List Of Important Alarms And Faults - Siemens Sinamics S120 Getting Started

Sinamics series
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Appendix

A.1

List of important alarms and faults

Axxxxx: Alarm
Fyyyyy: Fault
Table A- 1
The most important alarms and faults
Number Cause
F07085 Control parameters were compulsorily changed for the
following reasons:
They exceeded dynamic limits due to different
parameters.
They are not applicable because of properties of
the detected hardware that are not present.
Fault value (r0949, interpret as decimal):
Changed parameter number.
340: The automatic calculation of the motor and
control parameters was performed (p0340 = 1),
because the vector control was later activated
as a configuration (r0108.2).
F07802 Infeed or drive does not reply a 'ready' after an internal
actuation command.
Monitoring time too short.
DC link voltage not available.
Associated infeed or drive of the reporting
components defective.
Supply voltage incorrectly set.
Getting Started
Getting Started, (GS1) 04/2014, 6SL3097-4AG00-0BP3
Remedy
Not necessary.
No parameter change is necessary as the parameters
have already been limited to a reasonable level.
Extend monitoring time (p0857).
Ensure the DC link voltage. Check the DC link
voltage. Enable the infeed.
Replace associated infeed or drive of the reporting
components.
Check settings of the supply voltage (p0210).